Use in protective systems
Proline Prosonic Flow P 500 HART
20
Hauser
NOTICE
Once the SIL device has been locked, the process-related parameters are write protected,
and thereby locked, for security reasons.
It is still possible to read the parameters. When SIL locking is enabled, restrictions apply on all
communication options, such as the service interface, HART protocol and WirelessHART
protocol, local display and WLAN.
‣
Follow the specified locking sequence.
1. Ensure preconditions are met.
Current output 1
Setup
Low flow cut off
Current span
Failure mode
Assign
process variable
= 4...20 mA or
= 4...20 mA US
= 4...20 mA NAMUR or
= Min. or
= Max.
= Volume flow
= Off
A0043165-EN
2. In the
Setup
menu →
Advanced setup
submenu, select the
SIL confirmation
wizard.
3. Select the
Set write protection
parameter.
4. Enter the SIL locking code
7452
.
The device first checks the preconditions listed under item 1.
NOTICE
If these preconditions are not met, the message "SIL preparation = failed" appears on the
display along with the parameter that failed to meet the preconditions under 1.
The SIL confirmation sequence is not continued.
‣
Check preconditions.
If the preconditions are met, the message
SIL preparation = finished
appears on the display.
Once the preconditions have been met, the device automatically switches the following
parameters to safety-oriented settings: