– Page 6 –
2
Specifications
Standard Specification for iSaver 450 DPFC
Model
iSaver 450
Voltage Input
600 VAC 60Hz
Supply
Three Phase
Configuration
3 Phase – 4 Wire
Rating
450 kVAr
Current Rating
450A
Banks
1x50 +(4x100) kVAr
Sequence
1:2:2:2:2
Logic
The unit is designed to operate in steps of 50 kVAr
Minimum Step
70% of the lowest Bank Capacity (35 kVAr)
Control Operation
Controlled real time switching output based on load requirements.
Controller
Microcontroller based advanced electronic controller
Target Efficiency
> 98% (+/- 3%) for Canadian Voltage and frequency
iSaver Display
3 row crystal clear backlit LCD display of RMS values
Web Monitoring
On Line iSaver parameters display (PF, kVA, kVAh, kW, kWh, kVAr,
kVArh, Hz, V-THD, I-THD, Status, Alarms, Time Integrated data.
Diagnostic feature
iSaver internal key component functional analysis and status display
iSaver Monitor
Displays main and ISaver (panel) parameters locally and remotely
DG operation
Dedicated PF setting for DG operation
Displayed Data
PF, kVA, kVAh, kW, kWh, kVAr, kVArh, Hz, V-THD, I-THD
Main Protection
Short circuit and Over- load protection (MCCB 600A/50KA-3Pole)
Bank Protection
Short circuit and Over- load protection (MCCB & MCB) and Thermal
safety trip(s). Unit automatically resumes operation once fault is
corrected.
Protection
Thermostats operated over temperature protection of enclosure cham-
bers (Both Front and Capacitor Chamber), Harmonic Reactors and
Capacitors.
Construction
Robust Standalone metal enclosure (indoor application only)
Dimensions
2000 (H) x 1100 (W) x 750 (D) mm
Weight
620Kg [± 3 %]
Mounting
Floor Mounting with Foundation Bolts
Enclosure
Powder coated corrosion resistant sheet steel enclosure (RAL 7035)
Transient protection
Provided
Cable Entry
Bottom and side entry provision
.