Enatel DC System Manual
Page
18
of
26
Model: RWxxx
Version: 3.6
The following fuse is soldered to the PCB common to all models:
•
FH101 – 500mA 250V ETF Bussmann
•
Model specific fuses are listed as follows:
Table 4: Fuse specifications by model:
Model
FH1, FH2
RW 312U
5A 250V ceramic slow blow
RW 324U
5A 250V ceramic slow blow
RW 348U
5A 250V ceramic slow blow
RW 512U
10A 250V ceramic slow blow
RW 517U
10A 250V ceramic slow blow
RW 624U
10A 250V ceramic slow blow
RW 748U
10A 250V ceramic slow blow
6
S
ETTING
C
HANGES
All setting changes must be carried out by suitably qualified
personnel.
The rectifier is supplied from the factory with default parameters for normal operation.
These settings are detailed below.
To adjust the settings:
1.
Appropriate test equipment is necessary (depending on the adjustment), a
variable load, a variable DC power supply, an accurate voltage and current
meter are required.
2.
The rectifier should be unscrewed from its mounting.
3.
The rectifier must be disconnected from the battery and load.
N
OTE
: The trimpots to adjust the settings are accessible on the rear side of the rectifier.
Refer to