Lumberg IDC connectors (insulation displacement). Each terminal on the connector is 

rated at 16Amps at 50°C. 
To crimp the cable into the connector, simply insert the correct wire into the connector, 

and squeeze the connector in a vice or with a small press. Vice grips can be used 

provided a metal plate is used either side of the connection to protect the plastic. Once 

the connector has been crimped, it cannot be reused, so take great care to make sure 

that the correct wire and polarity colour is inserted before crimping. Additional spare 

connectors are available from the rectifier supplier. 

Figure 4: DC Connector 

 

3.4

 

Temperature Compensation 

Temperature Compensation Probes are available in different lengths. The end of the 

Temperature Compensation Probe should be attached to a terminal on a battery (the lug 

is isolated, so it doesn’t matter which terminal). Any excess cable should be neatly coiled. 

As the current in the Temperature Compensation Probe is minimal, it does not matter if 

the cable is longer than necessary (unlike the current carrying load and battery cables). 
 

 

Caution 

Do not reverse the polarity of the cables from the battery. 

This will blow an internal protection fuse, requiring the 

rectifier to be returned for servicing 

 
Do not connect the Temperature Compensation Probe to the rectifier until 

commissioning. See 

4

 

Commissioning the Rectifier

 

3.5

 

Multiple Rectifiers 

The rectifiers may be operated in parallel to provide greater current capability and to 

provide redundancy. 
When rectifiers are connected in parallel (and load sharing), alarm outputs on the 

rectifiers give the status of all the units. This means that you only need to connect one 

alarm card to the alarm circuitry when the rectifiers are connected in parallel. 
The load and battery cables should be wired in parallel to the rectifiers as per the diagram 

in section 2.3. Each rectifier should be fitted with a Temperature Compensation Probe 

connected to the same terminal on the same battery. 
For load and alarm sharing, an alarm and control interface cable should be connected to 

each parallel rectifier to ensure that all rectifiers load share automatically. When two or 

DC Connector 
4 Way Lumberg layout (viewed facing the front of the plug) 

Содержание RW312U

Страница 1: ...Installation and Operation Manual Model RW312U RW324U RW348U RW512U RW517U RW624U RW748U Series Rectifiers Version 3 6 Enatel DC System Manual...

Страница 2: ...andard Limited Warranty Policy on page 22 System Compliance Low Voltage Directive LVD 2014 35 EU Electromagnetic Compatibility Directive EMC 2014 30 EU Copyright Enatel 2020 All rights reserved Releas...

Страница 3: ...e Shutdown 8 2 11 Reverse Polarity Protection 8 2 12 Parallel Rectifier Operation 8 2 13 External Shutdown 9 2 14 Alarm Control Interface 9 2 15 Internal Alarm Card Optional 9 3 Installation 10 3 1 Ge...

Страница 4: ...atel Energy Standard Limited Warranty Policy 22 I A Warranty Exclusions and Restrictions 23 I B Battery Warranty 23 I C Initiating a Warranty Claim 23 I D Disclaimer 24 I E Remark 24 TABLE OF FIGURES...

Страница 5: ...10 240V 4A 12V 13 7V 11 5 15V 20A 300W RW324U 110 240V 4A 24V 27 4V 22 30V 10A 300W RW348U 110 240V 4A 48V 54 0V 45 60V 6A 300W RW512U 110 240V 8 5A 12V 13 7V 11 5 15V 35A 500W RW517U 110 240V 8 5A 17...

Страница 6: ...nsation Probe is connected and the rectifier fails the LED may not show The monitor external signals are still correct To verify the condition unplug the Temperature Compensation Probe 2 2 Display A r...

Страница 7: ...ttery ve supply the ve is common with the battery Do not connect the Battery and Load ve together The LVD voltage and the LVD Hysteresis voltage are pre set in the factory but may be adjusted to suit...

Страница 8: ...the rectifier may shut down until the allowed voltage is restored 2 9 Input Inrush Current Limiter On start up the peak mains inrush current is limited to twice the maximum operating current The outpu...

Страница 9: ...n allows remote monitoring of the rectifier The monitor connection is a RJ45 socket The pinout of the socket is as follows Table 3 Pin descriptions Pin Description Pin 1 Load Share signal 0 5V externa...

Страница 10: ...he rectifier To isolate the rectifier from the mains power unplug the IEC mains connector from the rectifier DANGER Do not operate the rectifier if the covers are damaged or removed in any way WARNING...

Страница 11: ...a minimum It is better to have a long mains lead and short low voltage cables The rectifier must be positioned so that airflow through the rectifier is not impeded in any way These rectifiers are conv...

Страница 12: ...battery and the rectifier to protect the rectifier load and battery The fuse should be mounted close to the battery and have a high rupture current capability just above the rectifier capability This...

Страница 13: ...ter if the cable is longer than necessary unlike the current carrying load and battery cables Caution Do not reverse the polarity of the cables from the battery This will blow an internal protection f...

Страница 14: ...parallel using an RJ45 cable to connect between the alarm and control interface the alarm outputs on the Alarm Card give the status of all the connected units This means that you only need one alarm c...

Страница 15: ...larm outputs share a Common contact 3 8 Rectifier Fail Mains Fail The Mains Fail Alarm is activated while the mains power is not present The Rectifier Fail Alarm can be configured to activate when the...

Страница 16: ...on of the current from the rectifier 5 Disconnect the mains then double check the polarity of the cables to the load and then plug them into the rectifier Re connect the mains 6 If there is more than...

Страница 17: ...t delivered by the rectifier is as expected Load Checks Connect battery but disconnect the main load to rectifier Connect a current meter in series with the battery Verify the current drawn by the bat...

Страница 18: ...slow blow 6 SETTING CHANGES All setting changes must be carried out by suitably qualified personnel The rectifier is supplied from the factory with default parameters for normal operation These settin...

Страница 19: ...Enatel DC System Manual Page 19 of 26 Model RWxxx Version 3 6 Figure 7 Trimpot Access Figure 8 Trimpot Functions Trimpot Access on product REAR See Figure 8 Trimpot Functions L R L R...

Страница 20: ...ely 10 seconds for the rectifier to switch back to Float Charge mode Check that the rectifier is in Float Charge mode as indicated on the LEDs Adjust the Float Voltage trimpot to set the required floa...

Страница 21: ...ge power supply across the load connections of the rectifier ensure that ve output of the variable supply is connected to the ve load connection Disconnect the Temperature Compensation Probe Connect a...

Страница 22: ...able voltage power supply up until the alarm activates Adjust the Alarm Output High trimpot to set the alarm limits Use the same procedure to adjust the Alarm Output Low limits See Figure 6 Alarm Conf...

Страница 23: ...arranty is not provided the authorized battery vendor s warranty shall be assigned to the batteries Note that batteries operational limits are typically more constrained than Enatel manufactured equip...

Страница 24: ...claiming implied warranties or warranties of merchantability all such warranties are limited to the greatest extent permitted by law Enatel reserves the right to change the information detailed within...

Страница 25: ...Enatel DC System Manual Page 25 of 26 Model RWxxx Version 3 6 This page is intentionally left blank...

Страница 26: ...Enatel 66 Treffers Road Christchurch 8042 New Zealand...

Отзывы: