Cautions and Warnings 

 

SET-UP DISTANCE ADJUSTMENT: 

As a general rule, the sensor should be fixed at a 15° to 20° angle from directly perpendicular to the 
target surface.  This will prevent direct reflected signal from glossy surfaces.  
 
To obtain maximum tolerance to distance variation, place the target at the greatest distance it is likely 
to be in the application, for example, flat against a guide surface.  Carefully adjust the sensor distance 
to  obtain  the highest reading on the white  background  and note  the reading.   Now move it  slightly 
further away, to get approximately 5% lower reading and fix sensor at that distance.  This will allow the 
target  to  move  closer,  back  to  the  highest  reading,  then  closer  still  down  to  5%  lower.    The  result 
should be a minimum of 2mm of allowable flutter with <5% change in reading. 

 

 

CAUTION: 

   The discrete output must not be connected to outputs from other sensors (i.e. outputs 

from  multiple  sensors  must  not  be  connected  in  parallel).    Parallel  connections  may 
damage sensor output circuitry. 

 

CAUTION: 

   Sensor is not suitable for wash down or hazardous environments; a separate enclosure 

with the appropriate ratings is recommended for these applications" 

 
 

IMPORTANT: 

This  product  is  an  accessory  or  part  of  a  system.    Always  read  and  follow  the  manufacturer’s 

instructions for the equipment before connecting this product.  Comply with all applicable codes and 
safety regulations.  Failure to do so may result in damage, injury or death. 

 

 

 

Certifications (CE, CSA, ETL)

 

 
ETL, CE, and CSA certifications are in process. 
 
 
 
 
 
 
 
 
 
 
 

Содержание CNTX Series

Страница 1: ...R U C T I O N S Operating Instructions 4564 Johnston Parkway Cleveland Ohio 44128 P 800 426 9912 F 216 518 9884 Sales Inquiries salessupport emxinc com Technical Support technical emxinc com www emxin...

Страница 2: ...CNTX Operating Instructions 1 Document no 10140104 Contents Cautions and Warnings 2 Product Overview 3 Specifications 4 Operation 5 Controls and Indicators 10 Connections 11 Ordering Information 12...

Страница 3: ...the target to move closer back to the highest reading then closer still down to 5 lower The result should be a minimum of 2mm of allowable flutter with 5 change in reading CAUTION The discrete output...

Страница 4: ...returning to the sensor is measured When the level is equal to or exceeds the threshold the discrete output changes state Due to the fast response of the sensor it is suitable for use in high speed a...

Страница 5: ...gment digits Digital Output Auto Detect PNP NPN Output Function NO NC Selectable Analog Output 0 5V of full scale 20mV resolution Security LOCK UN LOCK keypad Power indicator Green LED Detect indicato...

Страница 6: ...then closer still down to 5 lower The result should be a minimum of 2mm of allowable flutter with 5 change in reading 5 Place a sample or use the back cover of this manual with background into the se...

Страница 7: ...emory and are retained when power is removed To enter programming mode press and hold the P key for several seconds the LED intensity setting will be displayed Press and release the P key to scroll th...

Страница 8: ...fast enough rate to capture the signal The discrete output pulse can be extended from 0 to 90mS milliseconds in 10 mS increments as indicated by P0 though P9 on the display Press and release the T key...

Страница 9: ...o be taught the Undetect level Red indicates that the last attempt to teach resulted in an error If the error occurred during the teaching of the Detect level then the signal intensity was less than 0...

Страница 10: ...s or trends to be detected permitting corrective action to be taken Remote Lock Unlock Input The remote lock feature allows the user to lock out the local controls keys to prevent operators from makin...

Страница 11: ...rols and Indicators Indicators Green LED Threshold Mode while in Undetect Red LED Detect Yellow LED Threshold Mode while in Detect Display decimal points None illuminated LED low intensity One illumin...

Страница 12: ...uctions 11 Document no 10140104 Connections M12 Connector Wire Color Description Pin 1 Brown Power 10 to 24VDC Pin 2 White Discrete output PNP NPN NO NC Pin 3 Blue Ground Pin 4 Black Analog 0 5V Pin 5...

Страница 13: ...tructions 12 Document no 10140104 Ordering Information CNTX 30 0 Contrast sensor 3mm spot size CNTX 05 0 Contrast sensor 0 5mm spot size Accessories UVX300 BRKT UVX 300 C Bracket 5 meter cable with M1...

Страница 14: ...e or use other than intended design There is no warranty of merchantability There are no warranties expressed or implied or any affirmation of fact or representation except as set forth herein EMX Ind...

Страница 15: ...10140104 4564 Johnston Parkway Cleveland Ohio 44128 United States of America www emxinc com Technical Support 216 834 0761 technical emxinc com Sales 216 518 9888 Fax 216 518 9884 salessupport emxinc...

Отзывы: