30369-4-1013
Page 13
vERTICAL, 90° ELBOW TO HORIzONTAL OUT THE WALL
(REqUIRES 24” vERTICAL RISE)
Figure 13
90º ELBOW
“A”
PIPE
LENGTH
VENT CAP
WALL FIRESTOP/
THIMBLE
“C”
“B”
"A"
"B"
"C"
6"
11 1/4" to 12 3/4"
(286 mm to 324 mm)
4 3/4" to 6 1/4"
(121 mm to 159 mm)
9"
14 1/4" to 15 3/4"
(362 mm to 400 mm)
7 3/4" to 9 1/4"
(197 mm to 235 mm)
12"
17 1/4" to 18 3/4"
(438 mm to 476 mm)
10 3/4" to 12 1/4"
(273 mm to 311 mm)
INSTALLATION (continued)
CORNER INSTALLATION vERTICAL, 90° ELBOW TO
HORIzONTAL OUT THE WALL
(REqUIRES 24” vERTICAL RISE)
Figure 14
“A”
“C”
“B”
9” (229mm)
MINIMUM
VENT
CAP
“D”
6” (152mm)
MINIMUM
WALL FIRESTOP/
THIMBLE
1” (25.4mm)
MINIMUM
Dim.
DVL25FP
DVL33FP
A
37-13/16”
42-11/16”
B
26-3/4”
30-3/16”
C
14-1/16”
15-5/16”
D
53-1/2”
60-3/8”
Optional Blower Accessory
The Loft fireplace may be equipped with an optional FBB8 blower
accessory. See page 38.
The blower accessory may be installed at any time before or af-
ter installation of the fireplace providing that the junction box has
been properly pre-wired and secured to the right hand side of the
fireplace outer wrap. See Figures 10, 43 and 44.
Caution:
Wiring must be performed by a qualified electrician.
Note:
For shipping purposes, the junction box is installed on
the inside of the outer fireplace wrap. It is secured with
(2) screws on the side of the fireplace. Once removed
from the side of the fireplace, wiring to the junction box
and receptacle can be performed. Re-install the junc-
tion box assembly to the side of the fireplace so that the
receptacle faces inward. See Page 11, Figure 10.