Clearances

  1.  In selecting a location for installation, it is necessary to provide 

adequate  accessibility  clearances  for  servicing  and  proper 

installation.

  2. 

The DV4T-59-1, 5" to 9" wall depth is the standard vent 

kit provided with the DV-55T. See Accessories Page 6 to 

order vent kits for wall depths of 8" to 12" or 12" to 19". 

The use of tubes not supplied by the manufacturer results 

in unsatisfactory performance.

  3.  The DV-55T can be attached to the wall or recessed into the 

wall up to 4 inches in depth but the minimum 5 inches vent/air 

intake system  wall  depth  must  be  maintained. Example: If 

furnace is recessed into the wall at a depth of 4 inches, the 

minimum wall depth must be 9 inches.

  4.  The wall in which the furnace is recessed has (0) zero clearance 

to the furnace sides and top. 

  5.  When using side discharge registers, SOR-1 or SOK-1, the 

furnace cannot be recessed into the wall. 

  6.  Clearance to sidewall or combustible material is 4 inches.

  7.  Ceiling clearance is 4 inches.

  8.  Floor and rear wall clearance is (0) zero inches.

  9.  Clearance of 18 inches is required to sidewall or combustible 

material when flush mounted SOR-1, side outlet register is 

used. See Figure 4.

 10.  The minimum distance from the center of the vent cap to the 

nearest outside corner or obstruction is 24 inches. 

The vent terminal of a direct vent appliance with an input over 

50,000 BTU per hour shall be located at least 12 inches from any 

opening through which flue gases could enter a building. The bot-

tom of the vent terminal and the air intake shall be located at least 

12 inches above grade. 

WARNING: The nearest point of the vent cap should be a 

minimum horizontal distant of six (6) feet from any pres-

sure regulator. In case of regulator malfunction, the six 

(6) feet distance will reduce the chance of gas entering the 

vent cap.

Figure 4

  

Figure 3

Checking Manifold Pressure

Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 

regulator in the gas valve. Natural gas models will have a manifold 

pressure of approximately 4.0" w.c. at the valve outlet with the 

inlet pressure to the valve from a minimum of 6.0" w.c. for the 

purpose of input adjustment to a maximum of 7.0" w.c.  Propane 

gas  models  will  have  a  manifold  pressure  approximately  10.0" 

w.c. at the valve outlet with the inlet pressure to the valve from a 

minimum of 11.0" w.c. for the purpose of input adjustment to a 

maximum of 13.0" w.c. 
A 1/8" N.P.T. plugged tapping, accessible for test gauge connection, 

is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure 

and full on in 10 seconds.

CLEARANCES

Содержание DV-55T-1

Страница 1: ...eath or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas sup...

Страница 2: ...r Massachusetts 5 Introduction 6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and Maintenance Suggestions 15 How to Order Repair Parts 16 Parts List 16 Parts View 17 Service Notes 18 19 TABLE OF CONTENTS ...

Страница 3: ... control compartments burners and circulating air passageways of the appliance be kept clean DO NOT put anything around the furnace that will obstruct the flow of combustion and ventilation air DOkeeptheapplianceareaclearandfreefromcombustible material gasoline and other flammable vapors and liquids DO examine venting system periodically and replace damaged parts DO make a periodic visual check of p...

Страница 4: ...ights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new tanks or reinstal...

Страница 5: ...quiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall ...

Страница 6: ...tilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term qualified agency means any indi vidual firm corporation or company which either in person or through a representative is engaged in and is responsible for a the installation or replacement of gas piping or b the connection installation repair or servicing of equipment who i...

Страница 7: ...e to check for leaks Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the gas control to aid in servicing It is required by the National Fuel Gas Code that a drip line be in...

Страница 8: ...from the center of the vent cap to the nearest outside corner or obstruction is 24 inches The vent terminal of a direct vent appliance with an input over 50 000 BTU per hour shall be located at least 12 inches from any opening through which flue gases could enter a building The bot tom of the vent terminal and the air intake shall be located at least 12 inches above grade WARNING The nearest point ...

Страница 9: ...provided Side outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adjacent wall as shown in Figure 7 1 Locate and cut the 5 1 2 square opening in the cabinet side using the template from the kit exposing the inner liner knock out 2 Remove the knock out 3 Using the inner...

Страница 10: ...left and right side panels A three prong grounding plug assembly is located within the control compartment bottom of the furnace Please remove 7 8 knockout from appropriate side panel when routing plug assembly to an electrical outlet Installation of Three prong Grounding Plug Assembly 1 Disconnect nylon cap on 3 plug assembly from nylon plug on wiring harness Remove 3 plug assembly from control c...

Страница 11: ...isturbs the wind on one side of the air inlet section will result in back pressure on the flue section smothering the flame and eventual pilot outage When the vent cap is to be installed on siding or it appears that a projection within 6 of any side of the air inlet section could shield the air inlet section the entire vent should be supported away from the wall at least the distance of the projecti...

Страница 12: ...electric power to the appliance 15 Set thermostat to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions exactly B BEFORELIGHTINGsmellallaroundtheap...

Страница 13: ...v ing the burner door from the combustion chamber remove rear burner pilot burner and front burner With front and rear burners removed from furnace force water into the ribbon ports and dry with air pressure The correct pilot flame Figure 12 will be blue extending past the thermocouple The flame will surround the thermocouple just below the tip Natural gas pilots require adjusting when the inlet gas...

Страница 14: ...can be purchased plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can bepluggedintotheadapterandbeelectricallygrounded A7 8 hole is provided in the junction box for use with a conduit connector if local codes require this type of protection Thermostat Installation The thermostat should be ins...

Страница 15: ...nace is first installed or was off all summer the pilot flame may be too lean to ignite on the first few trials Turn the controlvalveknobtopilotpositionanddepresstheredresetbutton Holding the button down continually to bleed the line 1 Use lighter rod to light pilot with a match 2 Use the piezo ignitor at 30 second intervals until it lights If Electrode Does Not Produce Spark 1 Check wire connections...

Страница 16: ... a Part Number When ordering parts first obtain the Model Number from the name plate on your equipment Then determine the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of Gas Propane or Natural Do not order bolts s...

Страница 17: ...13118 7 0408 Page 17 PARTS VIEW ...

Страница 18: ...13118 7 0408 Page 18 SERVICE NOTES ...

Страница 19: ...13118 7 0408 Page 19 SERVICE NOTES ...

Страница 20: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact your dealer www empirecomfort com ...

Отзывы: