background image

12431-10-1008

Page 15

Replacing Fan and Oiling the Motor

The fan motor should be cleaned and oiled once each heating season. 

To reach the motor, withdraw the metal shroud surrounding the fan 

blade by removing the screws on each side. Oil holes are located 

on the top at each end of the motor. Use a few drops of #10 motor 

oil. To clean the motor, blow air through its ventilation openings 

with a vacuum cleaner or low pressure air source.
If fan motor is replaced, the silicone rubber gaskets, see Page 16, 

Index No. 4, Part No. 712059, should also be replaced. The gaskets 

must be stretched to fit the motor bolts into the gasket holes and then 

the motor and gaskets installed on the motor mounting bars.

GENERAL : 

All furnaces have been fire-tested to check for proper 

operation. This includes, main burner flame, pilot flame, fan opera-

tion, fan control, limit control and automatic valve operation. If 

the furnace fails to function on initial installation, it is advisable 

to re-check the following: 

1.  115 volts to the junction box.

2.  Inlet gas pressure.

3.  The 24 volt system.

4.  Type of gas being used and that shown on the rating label.

The Service Department at Empire Comfort Systems, Inc. may be 

contacted to assist in servicing furnace or call a qualified service-

man..

Servicing the Pilot and Main Burners, Pilot Orifice, Thermo-

couple, and Main Burner Orifices: 

Disconnect the gas supply 

at the inlet to the control valve. Then remove the burner door to 

which the above components are attached.

Servicing The  Fan  Motor: 

The  upper  front  panel,  the  shroud 

surrounding the fan blade and fan blade must be removed. See 

"Replacing Fan and Oiling the Motor" paragraph above.

Spark Igniter Does Not Light Pilot: 

With air in the gas line, such 

as when the furnace is first installed or was off all summer, the 

pilot flame may be too lean to ignite on the first few trials. Turn the 

control valve knob to pilot position and depress the red reset button. 

Holding the button down continually to bleed the line:

1.  Use lighter rod to light pilot with a match. 

2.  Use the piezo ignitor at 30 second intervals until it lights.

If Electrode Does Not Produce Spark:

1.  Check wire connections.

2.  Check gap for pilot burner to the electrode tip. Should be 

between 1/8" and 3/16". Electrode wire and tip must be more 

than 1/4" away from all other metal components.

If Pilot Does Not Light By Any Means:

1.  Check valve knob for being in the "Pilot" position.

2.  Check pilot adjustment for being full open (counterclockwise 

to open).

3.  If gas is available in the supply tubing, the pilot orifice and/or 

pilot burner is probably restricted by a spider web. Clean 

pilot assembly and relight.

If Pilot Does Not Remain On After Releasing Knob: 

1.  Follow  instructions  and  hold  button  down  longer  and 

harder.

2.  Determine if pilot flame extends past thermocouple; if not, 

adjust input or clean pilot burner.

3.  Replace thermocouple if millivolts read less than 15 mil-

livolts. 

Pilot Outage During Normal Operation:

1.  Check air inlet tube for a good tight fit at both ends (6" 

diameter tube).

2.  Check burner door and pilot hole cover for tight seal.

3.  Check input by manifold pressure gauge or gas meter.

Main Gas Valve Does Not Open When Thermostat Is Turned 

To On:

1.  Check  for  24  volts  to  valve  by  removing  one  wire  and 

touching to the 

SAME TERMINAL 

it was on. Terminal 

should  have a  light spark. 

DO NOT SHORT ACROSS 

TERMINALS, AS IT WILL BURN OUT THE WALL 

THERMOSTAT.

2.  Thermostat wires at the wall may be shorted, so check for 

a faulty thermostat.

3.  To check for line voltage to furnace, remove lower front 

panel and switch compartment cover and short across two-

terminal fan control to allow fan to operate.  (Figure 13)

SERVICE & MAINTENANCE SUGGESTIONS

Содержание DV-55SPP

Страница 1: ...se death or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other amma ble vapors and liquids in the v...

Страница 2: ...tts 5 Introduction 6 Speci cations 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 S...

Страница 3: ...appliance should be inspected before use and at least annually by a quali ed service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imp...

Страница 4: ...ghts perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption o...

Страница 5: ...iredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior...

Страница 6: ...e by a moving vehicle Quali ed Installing Agency Installation and replacement of gas piping gas utilization equip ment or accessories and repair and servicing of equipment shall be performed only by a...

Страница 7: ...e disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground...

Страница 8: ...istance from the center of the vent cap to the nearest outside corner or obstruction is 24 inches The vent terminal of a direct vent appliance with an input over 50 000 BTU per hour shall be located a...

Страница 9: ...0 x 1 screws provided Side outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 i...

Страница 10: ...e mountingplate Useadditionalcaulkingtocorrectunevenwall surface such as clapboard 2 Remove old furnace cement from ue outlet collar on com bustion chamber and collar of vent cap Remove old furnace ce...

Страница 11: ...it appears that a projection within 6 of any side of the air inlet section could shield the air inlet section the entire vent should be supported away from the wall at least the distance of the projec...

Страница 12: ...ectric power to the appliance 15 Set thermostat to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a re or explosion may result causing pro...

Страница 13: ...ing the burner door from the combustion chamber remove rear burner pilot burner and front burner With front and rear burners removed from furnace force water into the ribbon ports and dry with air pr...

Страница 14: ...ing can be purchased plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw With this wire completing the ground the appliance cord plug can bepluggedintotheada...

Страница 15: ...rnace is rst installed or was off all summer the pilot ame may be too lean to ignite on the rst few trials Turn the controlvalveknobtopilotpositionanddepresstheredresetbutton Holding the button down c...

Страница 16: ...Gasket for Burner Door 40 722040 Manifold Union 41 R 5655 Gas Valve VR8200C LP Gas 41 R 2148 Gas Valve VR8200C Natural Gas 42 UH 810 Transformer Mounting Bracket 43 R 1995 Transformer 44 UH 451 Juncti...

Страница 17: ...12431 10 1008 Page 17 PARTS VIEW...

Страница 18: ...12431 10 1008 Page 18 SERVICE NOTES...

Страница 19: ...12431 10 1008 Page 19 SERVICE NOTES...

Страница 20: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: