INstALLAtION pLANNING

Plan the furnace installation with three questions in mind:
1.  Where is the heat most needed in the house?
2.  Where should the furnace be so that it will vent properly?

3.  Where should it be placed so that it is not in home traffic areas 

or walkways?

Remember! Good Venting is essential to Good Heating.

vENtING

The installer must consider all of the following venting rules.  They 

will help plan where and how to install the furnace.
1.  Flue pipe MUST always have an upward slope (1/4 inch per 

foot minimum). 

see Figure 1.

Figure 1

2.  Flue pipe MUST NOT have any downward sloping sections, 

dips or sags. 

see Figures 2 and 3.

3.  Flue pipe MUST be Type B (double wall insulated).

Figure 2

Figure 3

NOtE: 

Do not use Type C single wall flue pipe.  

Uninsulated 

single-wall metal pipe shall not be used outdoors in 

cold climates for venting gas utilization equipment.

4.  For flue pipe running through walls, roof and within one (1) 

inch of combustible construction, use B-1 (one inch clearance 

to combustibles) vent pipe. 

see Figure 4

.  Any combustible 

material that is within 6 inches of the vent connection or the 

draft diverter must be shielded with a non-combustible material.

Figure 4

5.  Flue pipe MUST run as directly as possible and have as few 

elbows as possible.

6.  Flue  pipe  MUST  be  as  large  as  the  flue  collar  on  the  draft 

diverter. 

see Figure 5.

7.  The flue pipe MUST be on the outside of the draft diverter col

-

lar. 

see Figure 6.

8.  Each new piece of flue pipe that is connected when getting 

farther away from the furnace MUST connect on the outside 

of the previous one. 

see Figure 6. 

 Remember, the exhaust 

must flow "

into" the next pipe.

9.  The flue pipe MUST NOT be connected to a chimney that has 

a fireplace connected to it.

 see Figure 3.

Содержание 3588-4

Страница 1: ...tructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vici...

Страница 2: ...This series is design certified in accordance withAmerican National Standard Z21 86b 2002 by the Canadian Standards Association as a gravity type Floor Furnace and must be installed according to these...

Страница 3: ...be required due to excessive lint from carpeting bedding materials etc It is imperative thatcontrolcompartments burners andcirculating air passageways of the appliance be kept clean Do not use this h...

Страница 4: ...as can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clos...

Страница 5: ...sulated single wall metal pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 For flue pipe running through walls roof and within one 1 inch of combustible constru...

Страница 6: ...the roof through a closet re member that you MUST keep a minimum distance of 1 inch between Type B vent pipe and any combustible material See Figure 9 Run it through a single wall pipe that is 2 inche...

Страница 7: ...ion the additional furnace support and then nail the support in place by driving three nails into each end of it through the headers See Figure 10 12 Remove the jacks and supports 13 Make sure the fur...

Страница 8: ...ce between two joists because location is critical See Figure 10 If the location is not critical it is easier for you to put the furnace against a joist and then fill in with one additional support Do...

Страница 9: ...nominal pipe thread Use at least 1 2 inch pipe to avoid excessive pressure drop check lo cal codes Install the piping in accordance with the requirements described in Installation Planning Compounds...

Страница 10: ...average with the thermostat ON 140 minimum for valve to open 65 minimum for pilot to stay on Caution Label all wires prior to disconnection when servic ing controls Wiring errors can cause improper an...

Страница 11: ...TE The gas control rod is attached to the gas control knob 4 Push in gas control rod slightly and turn clockwise to OFF Note Rod cannot be turned from PILOT to OFF un less rod is pushed in slightly Do...

Страница 12: ...ural gas models should have a manifold pressure of approximately 3 5 w c at the valve outlet with the inlet pressure to the valve from a minimum of 5 0 w c for the purpose of input of input adjustment...

Страница 13: ...ust Street Hartford CT 06114 Phone 860 722 2433 Toll Free 800 243 9360 Fax 860 293 0479 Toll Free Fax 800 274 2004 Websites www fwwebb com www victormfg com Parts Heater Hearth and Grills MASTER PARTS...

Страница 14: ...32186 0 0513 Page 14 20 21 22A 22B 23 24 25 EXPLODED VIEW...

Страница 15: ...15L PILOT BURNER WITH THERMOPILE LP GAS 12 602032 23218 23217 BURNER 13 732010 FF250 FF250 ELECTRODE AND WIRE 14 R2313 R2313 R2313 PIEZO IGNITOR 15 742169 P8631 P8625 BURNER ORIFICE NATURAL GAS 15 742...

Страница 16: ...ppliance for service What Is Not Covered Damages that might result from the use misuse or improper installation of this appliance Travel diagnostic costs and freight charges on warranted parts to and...

Отзывы: