36092-10-0619
Page 16
GAS SUPPLY
The gas pipeline can be brought in through the vent-end of the
fireplace only. Consult the current National Fuel Gas Code, ANSI
Z223.1 installation code.
RECOMMENDED GAS PIPE DIAMETER
Pipe
Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
(Dimensions in Inches)
Natural
Propane
Natural
Propane
0-10 feet
1/2
3/8
1/2
3/8
10-40 feet
1/2
1/2
5/8
1/2
40-100 feet
1/2
1/2
3/4
1/2
100-150 feet
3/4
1/2
7/8
3/4
NOTICE:
Never use plastic pipe. Check to confirm whether your
local codes allow copper tubing or galvanized.
NOTICE:
Since some municipalities have additional local codes,
it is always best to consult your local authority and installation
code.
The use of the following gas connectors is recommended:
— ANSI Z21.24 Appliance Connectors of Corrugated Metal
Tubing and Fittings.
— ANSI Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The Commonwealth of Massachusetts
requires that a flexible appliance connector cannot exceed three
feet in length.
2”
2”
SHUT-OFF VALVE
INCLUDED IN
ENVELOPE PACK
FRONT
TOP
8-3/4”
8-3/4”
Figure 12
GAS SUPPLY PRESSURE (INCHES W.C.)
Minimum
Normal
Maximum
Natural Gas
4.5
7.0
14.0
Propane Gas
10.8
11.0
14.0
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas
3.5
Propane Gas
10.0
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required
by the National Fuel Gas Code that a drip leg be installed near
the gas inlet.
See Figure 13.
This should consist of a vertical
length of pipe tee connected into the gas line that is capped
on the bottom in which condensation and foreign particles may
collect.
Figure 13
Figure 14
Содержание MILLIVOLT DVCP36PP30N
Страница 45: ...LOG PLACEMENT LSU24SPF 36092 10 0619 Page 45...
Страница 66: ...36092 10 0619 Page 66 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING...
Страница 67: ...36092 10 0619 Page 67 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING...
Страница 71: ...36092 10 0619 Page 71 This page intentionally left blank...