38714-5-0920
Page 31
Figure 39
Acceptable vertical and horizontal vent run.
Unacceptable vertical and horizontal vent run.
Venting Graph (Dimensions in Feet)
VER
TICAL
DIMENSION
FROM
THE
BOTT
OM
OF
THE
UNIT
T
O
THE
CENTER
OF
THE
FLUE
OUTLET
WITH
VER
TICAL
OR
HORIZONT
AL
TERMINA
TION
CAPS
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
HORIZONTAL RUN
REAR EXIT - VERTICAL AND HORIZONTAL TERMINATION
(DIMENSIONS IN FEET)
REAR HORIZONTAL
VENT CONNECTION
B
A
NOTE: FLEX VENT
MAXIMUM HEIGHT
IS 35 FEET
To Use the Vent Graph (Figure 39)
1. Determine the height of the center of the
horizontal vent pipe. Using this dimension on the
Sidewall Vent Graph, locate the point it intersects
with the slanted graph line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
unit in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is
12 feet, 4 inches the horizontal run to the outer wall
flange must not exceed 12 feet, 3 inches.
EXAMPLE B:
If the vertical dimension from the floor of the unit is
6 feet, 9 inches, the horizontal run to the outer wall
flange must not exceed 6 feet, 6 inches.
SPECIAL NOTE:
For each 45 degree elbow installed
in the horizontal run, the length of the horizontal
run MUST be reduced by 18" (45cm). This does
not apply if the 45-degree elbows are installed on
the vertical part of the vent system. Reduce 3' for
every 90-degree elbow.
Example:
According to the chart the maximum
horizontal vent length is 20' and if two 45-degree
elbows are required in the horizontal vent it must
be reduced to 17'.
The maximum number of 45 degree elbows permitted
per side wall installation is two (2). These elbows can
be installed in either the vertical or horizontal run.
VENTING FIREPLACE - REAR