26408-0-1009
Page 18
Figure 25
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE WALL
HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW OFF TOP OF
FIREPLACE
positioning the Fireplace
Determine the exact position of the appliance so the direct vent termination
will be centered (if possible) between two (2) studs. This will avoid any
extra framing. All vent kit pipes should be assembled on the unit after the
unit is moved into the final position.
Cutting the Hole (Figures 25)
After the fireplace has been positioned in its permanent location, the
hole through the exterior wall of the house can be cut. This hole must be
10" (254mm) high x 10" (254mm) wide with its center line determined
by the amount of vertical rise and horizontal run of the termination.
See Figure 25.
When locating the hole it must be noted that the bottom of
the cap must be 12" (305mm) above the ground level, and top of the cap
must be no less than 18" (457mm) below a combustible projection, and no
closer than 9" (229mm) to any wall running parallel to vent termination.
See Figure 26.
Lp and Nat models
minimum
Figure 26
Figure 27
FIREpLACE
SERIES
HARD ELBOW DIMENSIONS
"A"
"B"
"C"
Dvp36Dp
43-1/2"
(1105mm)
4"
(102mm)
6"
(152mm)
FIREpLACE
SERIES
FLEX pIpE 90 DEGREE BEND
"A"
"B"
"C"
Dvp36Dp
45"
(1143mm)
4-1/2"
(114mm)
6-1/2"
(165mm)
Lp and Nat models
Lp and Nat models
vENTING FIREpLACE - TOp (continued)