31451-2-1013
Page 20
VENTING FIREPLACE - TOP (continued)
Figure 27
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH
THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE
ELBOW OFF TOP OF FIREPLACE
Positioning the Fireplace
FIREPLACE
SERIES
HARD ELBOW DIMENSIONS
"A"
"B"
"C"
DVP36DP
43-1/2"
(1105mm)
4-1/2"
(114mm)
6-1/2"
(165mm)
FIREPLACE
SERIES
FLEX PIPE 90 DEGREE BEND
"A"
"B"
"C"
DVP36DP
45"
(1143mm)
4-1/2"
(114mm)
6-1/2"
(165mm)
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location, the
hole through the exterior wall of the house can be cut. This hole must be
11" (280mm) high x 10" (254mm) wide with its center line determined
by the amount of vertical rise and horizontal run of the termination.
See Figure 27.
When locating the hole it must be noted that the
bottom of the cap must be 12" (305mm) above the ground level,
and top of the cap must be no less than 18" (457mm) below a
combustible projection, and no closer than 9" (229mm) to any wall
running parallel to vent termination.
See Figure 28.
Figure 28
Figure 29
Содержание DVP36DP31 Series
Страница 21: ...31451 2 1013 Page 21 Figure 30 Figure 31 Figure 32 EXAMPLES TOP VENT RUN...
Страница 37: ...31451 2 1013 Page 37 Figure 57 DVVK 4FV DIRECT VENT TERMINATION KIT...
Страница 47: ...31451 2 1013 Page 47 Figure 70 MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM...
Страница 59: ...31451 2 1013 Page 59 INTERMITTENT PILOT CONTROL SYSTEM TROUBLESHOOTING...
Страница 68: ...31451 2 1013 Page 68 PARTS VIEW...