VENTINg FIREPLACE (cont.)
Sidewall Venting
The maximum vertical and horizontal distances are 25 feet and 12
feet, respectively. Vertical dimensions are based on top of fireplace
to centerline of pipe. Horizontal dimensions are based on centerline
of pipe to termination.
CAUTION:
Total vertical run MUST BE completed before starting
horizontal run.
Horizontal chimney run must slope upward
(away from fireplace) 1/4" per foot and vent termination
must be level.
Under no circumstances should combustible materials (including
siding) be closer than 2" from the top of the 6 5/8" pipe or closer
than 1" on the side and bottom.
Cutting the Hole (Figure 7)
After the appliance has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
needs to be 10" high x 10" wide square with its center line determined
by the amount of vertical arise and horizontal run of the termination.
When locating the hole it must be noted that the bottom of the cap
must be 12" above the ground level, and top of the cap must be no
less than 18" below a combustible projection, and no closer than
9" to any wall running parallel to vent termination.
VENT CAP
9” (229MM) TO SIDE WALL
Figure 7
Figure 6
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
VENTING MUST
TERMINATE IN
THIS AREA
HORIZONTAL RUN IN FEET
VER
TICAL
RISE
ABOVE
FIREPLACE
IN
FEET