The main burner flame and pilot flame must be checked for 

proper  flame  characteristics,  as  outlined  in  the  Installation 

Instructions and Owner's Manual.
VERIFYING INPUT RATE OF CONVERTED APPLIANCE

The input of the appliance must be checked as follows:

1.  Turn off all other gas appliances. Clock the gas meter and 

determine the number of seconds required to consume one 

cubic foot of gas.

2.  3600 ÷ time (in seconds) = cu. ft. per hour.

3.  Then cu. ft. per hour x heating value of gas = input rate (Btuh). 

On installation without gas meters, check manifold for proper 

pressure.

PLACEMENT OF CONVERSION LAbELS

1.  Conversion label R1322 is to be placed in a location visible 

when all appliance panels are installed.

2.  Gas conversion label R1321 is to be placed near the gas valve.
If appliance is not installed or warranty card has not been returned 

to Empire Comfort Systems, Inc., check off type of gas converted 

to on card. Also, indicate conversion by adding “Conv.” behind gas.
The main burner flame and pilot burner flame must be checked 

for proper flame characteristics, as outlined in the  Installation 

Instructions and Owner’s Manual.

VERIFYING INPUT RATE OF CONVERTED FIREPLACE

The input of the fireplace must be checked as follows:

1. Turn off all other gas appliances. Clock the gas meter and 

determine the number of seconds required to consume one 

cubic foot of gas.

2.  3600 ÷ time (in seconds)  = cu. Ft. per hour.

3.  Then cu. Ft. per hour x heating value of gas = input rate 

(Btuh). On installation without gas meters, check manifold 

for proper pressure.

If fireplace is not installed or warranty card has not been returned 

to Empire Comfort System’s, Inc., check off type of gas converted 

to on card. Also, indicated conversion by adding “Conv.” behind 

type of gas.