REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part for 

residential  purposes,  including  those  owned  or  operated  by  the 

Commonwealth and where the side wall exhaust vent termination 

is  less  than  seven  feet  above  finished  grade  in  the  area  of  the 

venting,  including  but  not  limited  to  decks  and  porches,  the 

following requirements shall be satisfied:

1.  INSTALLATION OF CARBON MONOXIDE DETECTORS. 

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter shall 

observe that a hard wired carbon monoxide detector with an 

alarm and battery back-up is installed on the floor level where 

the gas equipment is to be installed. In addition, the installing 

plumber  or  gas  fitter  shall  observe  that  a  battery  operated 

or  hard  wired  carbon  monoxide  detector  with  an  alarm  is 

installed on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner 

to secure the services of qualified licensed professionals for 

the installation of hard wired carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery  back-up  may  be  installed  on  the  next  adjacent 

floor level.

 

b.  In  the  event  that  the  requirements  of  this  subdivision 

can not be met at the time of completion of installation, 

the owner shall have a period of thirty days to comply 

with  the  above  requirements;  provided,  however,  that 

during said thirty day period, a battery operated carbon 

monoxide detector with an alarm shall be installed.

2.  APPROVED CARBON MONOXIDE DETECTORS. Each 

carbon monoxide detector as required in accordance with the 

above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and IAS certified. 

3.  SIGNAGE.  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum  height  of  eight  feet  above  grade  directly  in  line 

with the exhaust vent terminal for the horizontally vented 

gas fueled heating appliance or equipment. The sign shall 

read, in print size no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL 

OBSTRUCTIONS”.

4.  INSPECTION. The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment shall not 

approve the installation unless, upon inspection, the inspector 

observes  carbon  monoxide  detectors  and  signage  installed 

in accordance with the provisions of 248 CMR 5.08(2)(a) 1 

through 4.

 

(b)  EXEMPTIONS: The following equipment is exempt from 

248 CMR 5.08(2)(a)1 through 4: 

    1.  The equipment listed in Chapter 10 entitled 

“Equipment Not Required To Be Vented” in the most 

current edition of NFPA 54 as adopted by the Board; 

and 

 

 

2.  Product Approved side wall horizontally vented gas 

fueled equipment installed in a room or structure 

separate  from  the  dwelling,  building  or  structure 

used in whole or in part for residential purposes. 

 (d) 

MANUFACTURER REQUIREMENTS - GAS 

EQUIPMENT VENTING SYSTEM NOT PROVIDED. 

When the manufacturer of a Product Approved side 

wall horizontally vented gas fueled equipment does not 

provide the parts for venting the flue gases, but identifies 

“special  venting  systems”,  the  following  requirements 

shall be satisfied by the manufacturer:

 

 

1.  The referenced “special venting system” instructions 

shall  be  included  with  the  appliance  or  equipment 

installation instructions; and

 

 

2.  The  “special  venting  systems”  shall  be  Product 

Approved  by  the  Board,  and  the  instructions  for 

that system shall include a parts list and detailed 

installation instruction.

 

(e)  A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions 

shall remain with the appliance or equipment at the 

completion of the installation. 

Содержание DVLT36FP92N-2

Страница 1: ...N P 2 DVTT36FP92 N P 2 Traditional DVTT42FP92 N P 3 UL FILE NO MH45034 GAS FIRED WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or prop...

Страница 2: ...o install the unit See page 9 4 Frame the opening See page 10 5 Install the gas lines See page 8 6 Install the wiring See page 42 7 Install the venting See pages 14 19 8 Install the fireplace See page...

Страница 3: ...ION 37 BARRIER INSTALLATION 38 MULTIFUNCTION REMOTE LIGHTING INSTRUCTIONS 39 MULTIFUNCTION REMOTE OPERATING INSTRUCTIONS 40 41 MULTIFUNCTION REMOTE WIRING DIAGRAM 42 PREMIUM MULTIFUNCTION REMOTE OPERA...

Страница 4: ...the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code or CSA B149 1 in Canada Available from theAmerican National Standards Institute Inc 11 West 42nd St New York N...

Страница 5: ...7 14 70 14 7 KWH Minimum 6 7 6 7 7 3 7 8 Orifice Front 43 1 35 mm 39 53 Orifice Rear 43 55 39 53 Air Shutter Opening Front DVLT36 1 8 DVTT36 3 8 DVLT36 1 4 DVTT36 Wide Open DVLT42 1 8 DVTT42 3 8 DVLT4...

Страница 6: ...he interior depth of the firebox not shown 18 7 8 18 7 8 H The height to the firebox standoffs 51 5 16 57 5 16 I Width from the left side of the box to the centerline of vent 27 1 2 30 1 2 J Depth fro...

Страница 7: ...ng a television above a fireplace has become a desirable feature however the following information should be considered All fireplaces whether decorative or heater rated create heat Most television ma...

Страница 8: ...of liquefied petroleum gases The gas lines must be checked for leaks by the installer This should be done with a soap solution watching for bubbles on all exposed connections and if unexposed a press...

Страница 9: ...al portion of the vent system does not exceed 20 feet 6 096mm with a minimum vertical run of 8 feet 2 438mm See details in Venting Section See Figure 7 CORNER INSTALLATION ANGLED CORNER INSTALLATION I...

Страница 10: ...ed and the appliance is installed directly on carpeting tile or other combustible material other than wood flooring it shall be installed on a metal or wood panel extending the full width and depth of...

Страница 11: ...sh Wall Installation 1 2 12 mm NON COMBUSTIBLE NON COMBUSTIBLE FINISHED WALL ALL FIREPLACE METAL MUST BE COVERED WITH NON COMBUSTIBLE MATERIAL ONLY TOP OF FIREPLACE OPENING IMPORTANT NO FINISHING MATE...

Страница 12: ...NING If the joints between the finished wall and the fireplace surround top and sides are sealed a 300 F minimum sealant material must be used These joints are not required to be sealed Only non combu...

Страница 13: ...THIMBLE WALL FIRESTOP DVLT DVTT36 DVLT DVTT42 A 72 11 16 1853 mm 77 1 4 1962 mm B 51 9 16 1310 mm 54 5 8 1387 mm C 25 11 16 652 mm 27 7 8 708 mm D 103 1 8 2620 mm 109 1 4 2775 mm E 19 11 16 500 mm 21...

Страница 14: ...dewall Vent Graph locate the point it intersects with the slanted graph line 2 From the point of this intersection draw a vertical line to the bottom of the graph 3 Select the indicated dimension and...

Страница 15: ...ired vent terminal clearances of 12 305mm above grade level a snorkel kit is recommended It allows installation depth down to 7 178mm below grade level The 7 178mm is measured from the center of the h...

Страница 16: ...s total of maximum horizontal dimensions The maximum vertical and horizontal distances for two 90 elbows as shown in Figure 27 is 37 feet FIRESTOP AT CEILING LEVEL SEE GRAPH FOR PERMISSIBLE H AND V DI...

Страница 17: ...ts center line determined by the amount of vertical rise and horizontal run of the termination See Figure 28 10 3 8 263 5mm 12 3 8 314 3mm Figure 28 When locating the hole it must be noted that the bo...

Страница 18: ...en the minimum required vertical is 6 H 8 45 90 90 14 equivalent horizontal From the graph the required vertical is 6 Figure 30 DV LT TT 42 EXAMPLE If total horizontal needs to be 10 then the minimum...

Страница 19: ...age 19 EXAMPLES VENT RUN EXAMPLE If total vertical is to be 9 then the maximum required horizontal run can be 14 H 20 45 45 14 equivalent horizontal From the graph the required vertical is 14 Figure 3...

Страница 20: ...tcrop the vent pipe must extend outward so that the horizontal vent termination is located flush to or beyond the outcrop siding Information on Various Venting Routes and Components Important It is al...

Страница 21: ...f 2 feet 61 cm from the cen ter line of the terminal 18 in 46 cm minimum 18 in 46 cm minimum L Clearance above paved sidewalk or paved drive way located on public property 7 ft 2 13 m E Clearance to u...

Страница 22: ...t end with four equally spaced indented sections When the internal beads of each starting outer pipe line up rotate pipe section clockwise 90 approximately 3 inches The vent pipe is now locked togethe...

Страница 23: ...equire the use of wall firestops on both sides of the wall through which the vent passes Cut an appropriate sized hole in wall See Figure 36 Position firestop on interior side of wall for hole Attenti...

Страница 24: ...sses through an interior wall an exterior wall or a ceiling These firestops act as a firebreak heat shield and as a means to insure that minimum clearances are maintained to the vent system Horizontal...

Страница 25: ...eiling is an attic position and secure the firestop on top of the previously framed hole See Figure 41 Notice Remove insulation from the framed area in the attic before installing the firestop and or...

Страница 26: ...e this nail through this center point Make the outline of the roof hole around this center point Notice Size of the roof hole dimensions depend on the pitch of the roof There must be a 1 inch clearanc...

Страница 27: ...INATION Installing the Vent System in a Chase A chase is a vertical box like structure built to enclose the gas appliance and or it s vent system Vertical vent runs on the outside of a building may be...

Страница 28: ...b Two sets of 45 degree elbow offsets within these vertical installations From 0 to a maximum of 8 ft a vent pipe can be used between elbows c Wall straps must be used to support offset pipe every 4 T...

Страница 29: ...t Ember Chunk with pin I Part Number 29135 Left Ember Bed Chunk B Part Number 29127 Left Branch J Part Number 29133 Ember Bed Front C Part Number 29128 Center Branch K Part Number 29122 Left Rear Log...

Страница 30: ...34829 1 0115 Page 30 Figure 47 36 BOTTOM LOG PLACEMENT B I H A C J M K L E DVTT36 LOG PLACEMENT...

Страница 31: ...ire tie and set the grate aside 5 Place liner bottom into firebox 6 Place log grate into firebox The front bar will butt up against the burner 7 Place the Right Ember Bed Chunk A between the right fro...

Страница 32: ...og E 15 Place the Right Branch L onto the right pin on the Left Rear Log E and the top of the Center Ember Chunk H The end of the log will float and touch the log grate bar on the right DVTT36 LOG PLA...

Страница 33: ...124 Left Ember Chunk I Part Number 29133 Ember Bed Front C Part Number 29127 Left Branch J Part Number 29134 Ember Bed Front Extension D Part Number 29128 Center Branch K Part Number 29122 Left Rear L...

Страница 34: ...34829 1 0115 Page 34 DVTT42 LOG PLACEMENT Figure 49 42 BOTTOM LOG PLACEMENT B I H G A D C J M K L E F N...

Страница 35: ...astic wire tie and set the grate aside 5 Place liner into firebox 6 Place log grate into firebox The front bar will butt up against the burner 7 Place the Right Ember Bed Chunk A between the right fro...

Страница 36: ...pin of the Left Rear Log E and on top of the Left Ember Burner Chunk The end of the log will rest on the left log grate bar 17 Place the Center Branch K between the two middle log grate bars on the m...

Страница 37: ...ace the glass media around the Accent Burner Fill the me dia basket until the glass media covers the burner with only one layer of glass Do not place any of the glass media inside the pilot guard 4 Re...

Страница 38: ...5 Page 38 BARRIER INSTALLATION KEEP SCREEN FLANGES IN FRONT OF GLASS FRAME FLANGES WHEN INSTALLING GLASS FRAME SCREEN FRAME Note A barrier is required for operation of the appliance Figure 52 Figure 5...

Страница 39: ...if applicable 2 Open bottom louver assembly 3 Locate On Off gas cock and turn clockwise to OFF Do not force 4 Close bottom louver assembly 1 STOP Read the safety information above 2 Turn OFF electric...

Страница 40: ...emote control receiver which allows the user to program the hand held remote transmitter 1 There is a switch located on the right side of the Control Mod ule that reads REMOTE OFF 2 When the remote of...

Страница 41: ...annot be reached call the fire department 2 The gas control must be replaced if it has been flooded with water Call a qualified service technician 3 The gas control is a safety device It must be repla...

Страница 42: ...2 MULTIFUNCTION REMOTE WIRING DIAGRAM Figure 56 Notice For Multi Function Remote Fireplace models with Premium Multi Function Remote Control Refer to the separate instructions for operation of the rem...

Страница 43: ...UNTDOWN TIMER P2 PROGRAM 2 ON P2 PROGRAM 2 OFF BATTERY LOW CONTINUOUS PILOT CONTINUOUS PILOT CHOICE ROOM ROOM TEMPERATURE SET THERMOSTAT SETTING OFF ON THERMO DISPOSITION OF HEATER FAN REAR MAIN REAR...

Страница 44: ...ternal components of the Main Module reach 170 F the unit will automatically shut off and send a repetitive audible signal The unit can be turned back on when the module cools below 160 Communication...

Страница 45: ...5 below set temperature Flame Level 7 Manual Flame Modulation Main Flame To change the Flame Level manually press the FLAME MAIN button The current level will show in the MAIN box on the LCD screen 1...

Страница 46: ...annually by a qualified service person Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the air flow Glass Cleaning It will be necessary to clean the gl...

Страница 47: ...REST HERE Figure 58 4 Grasp the glass frame on the top and the bottom Pull the glass straight out to disengage the glass from the fireplace Pull the bottom out of the opening first and then guide the...

Страница 48: ...sembly NAT 15 R10918 R10918 Pilot Assembly LP 16 R10898 R10899 Back Burner 17 28304 28303 Mesh 18 R10915 R10915 Flex Straight 19 28269 28269 Media Basket Leg 20 28256 28257 Media Basket 21 28319 28312...

Страница 49: ...49 DVLT 36 42 FP92 EXPLODED VIEW Use Only Manufacturer s Replacement Parts Use of Any Other Parts Could Cause Injury Or Death 25 26 27 28 29 30 10 9 1 3 2 4 5 8 6 22 7 11 12 13 14 15 17 19 16 18 21 2...

Страница 50: ...R10900 R10901 Burner Tube 16 R10914 R10914 Pilot Assembly Nat 16 R10918 R10918 Pilot Assembly LP 17 28300 31148 Burner Assembly 18 R11167 R11167 Flex 90 Degree 19 28275 28275 Valve Mount Plate 20 R108...

Страница 51: ...34829 1 0115 Page 51 DVTT 36 42 FP92 EXPLODED VIEW 1 3 2 4 5 7 6 8 9 13 12 19 22 14 17 20 15 16 11 18 29 21 23 25 26 27 28 30 10 24...

Страница 52: ...be ordered by your Service Person or Dealer Proof of purchase is required for warranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number an...

Страница 53: ...oesn t hold the burner cover up Move any beads out of the way if it does 11 Re attach the grate down with the two screws Replace the glass media over the burner NOTE The lamp will pull straight out of...

Страница 54: ...th clean dry cloth NOTE The lamp will pull straight out of the socket When re installing ensure integrity of gasket seal Replacement Bulbs Replacement bulbs are available locally at most hardware appl...

Страница 55: ...Owner The appliance must be installed by a qualified installer and operated in accordance with the instructions furnished with the appliance A bill of sale cancelled check or payment record should be...

Страница 56: ...r this appliance Any safety screen guard or barrier removed for servicing an appliance must be replaced prior to operating the appliance Due to high temperatures the appliance should be located out of...

Страница 57: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clo...

Страница 58: ...ns shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum h...

Страница 59: ...34829 1 0115 Page 59 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 60: ...t Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please contact...

Отзывы: