DESCTIPTION OF COMPONENTS
GB
GB
GB
GB
7. LIST OF PARAMETERS IN THE "SMART MT"
Menu parameters list "Set" 2-2
Menù
label
Par Label Description
U.m.
Range
Default C-TH
PW Address
min
max
SAni
133
CYCA
Frequency activation heat treatment DHW (Legionella)
How often should the treatment be carried out legionella. If 0, the
function is disabled
day
0
30
0
S
16405
134
SEtA
Set point heat treatment DHW (legionnaires)
°C
50
70
60
S
16407
135
tiMA
Period activation heat treatment (SWH antilegionnaires)
Minimum time continued, in which the temperature of the water in
the accumulation is maintained higher than the set point
min
1
30
15
S
16407
136
HouA
Orario attivazione trattamento termico DHW (antilegionella)
h:
min
00:00 23:59 02:00
S
16408
EHS
137
OPEr
Activation mode of the heat generators:
0: Disabled additional generator
1: When the additional generator activates, the heat pump turns off.
2: When the additional generator activates, the heat pump remains on.
-
0,1,2
0
S
16409
138
SEtO
Bivalence set point (additional generator):
External temperature at which the free contact can be activated. Heat
Source (clamps F-L)
° C
-15
10
5
S
16410
139
dELt
Bivalence delay (additional generator):
On-going time where the external temperature is below the Bivalence
set point, until the free contact activates. Heat Source (clamps F-L)
min
1
120
30
S
16411
AL
AMbt
Failure of the environment temperature probe CHRONO-TH (see
paragraph 10.2)
9004
AMbH
Failure of the environment humidity probe CHRONO-TH (see para-
graph 10.2)
9005
OUtA
Failure of the external temperature probe CHRONO-TH (see para-
graph 10.2)
9006
OUtU
Failure of the outlet water temperature probe CHRONO-TH (see
paragraph 10.2)
9007
InU
Signal error “Temp. Water Supply System” (clamps 3-4) see para-
graph 10.2)
9008
SAnt
Failure of the sanitary accumulation temperature probe CHRONO-TH
(see paragraph 10.2)
9009
HP
Heat pump error. Error code on the PCB display (see paragraph 10.3)
9010
rEmC
Remote controller connecting error (see paragraph 10.2)
9011
CONd
Condensation risk for the radiant cooling system (see paragraph
10.2)
9013
SUrr
Overheating risk for the radiant heating system (see paragraph 10.2)
9014
Menu parameters list “Set”:
X=Parameter also available on CRONO-TH
S = Password Service