Installation of "CRONO-TH" user terminal
• Be sure to comply with standards concerning
electric equipment to perform installation and
low power connection between the HP and the
CRONO-TH.
• Disconnect electrical power from the HP before
wiring the CRONO-TH.
• Use cable Modbus Belden 8762, or similar cable to
wire CRONO-TH
• The maximum length of the connection cable of the
CHRONO-TH is 100 m
Notes for installation of CRONO-TH
• Never install CRONO-TH above a stove or gas
heater or any other combustion device to avoid
damaging the electronic components and defor-
ming the outer casing.
• Do not install it in places exposed to steam coming
from stoves, pans or similar equipment, or expo-
sed to water or sprays from taps or the likes.
• Do not install in a position which is
exposed to direct sunlight.
• Install CRONO-TH in the same room as the radiant
system.
• Do not install in a room where industrial chemical
agents are used (ammonium, sulphur, chlorine,
ethylene compounds, acids, etc.).