Process Set - Alarm Set
HYS
ON
OFF
Process
Set
Process Set + Alarm Set
Alarm
Output
Process Value
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process
Set
Process Set + Alarm Set
Alarm
Output
Process Value
Deviation band alarm
Deviation range alarm
it can be adjusted from 0% to 50% of process input scale
(
-
) It is active if logic output function of Alarm Output-2 is
alarm output.
Alarm- 2 hysteresis value.
Alarm
Status
Alarm
Output
On
Delay
OFF
Delay
Alarm off delay time for Alarm Output-2. It can be adjusted from 0 to
9998 seconds. When the value is greater than 9998,
is seen on
the screen. It means alarm latching output is selected. It is active if logic
output function of Alarm Output-2 is alarm output.
Alarm on delay time for Alarm Output-2. It can be adjusted from 0 to
9999 seconds. It is active if logic output function of Alarm Output-2 is
alarm output.
“Aln2 Conf” Menu is accessible if
parameter in “PCnF ConF” is
Alarm stabilisation time for Alarm Output-2. It can be adjusted from 0 to
99 second. It is active if logic output function of Alarm Output-2 is alarm
output. After the unit is power-on and Alarm Stabilisation Time is
expired, if an alarm condition which is selected with Alt2 is present,
then Alarm output-2 becomes active.