2. Attach the weather angles to the chassis using
the screws provided.

3. Slide chassis into wall sleeve, assuring that wall
sleeve studs on the wall sleeve flanges align with
the holes in the weather angles.

4. Attach left and right weather angles to wall
sleeve using the two 1/4-20 nuts provided.

5. Install plenum and duct work.

6. Plug in the supplied low voltage harness and
run it to the wall thermostat as shown in the unit’s
wire diagram.

CONDENSATE DRAIN

The VPAC/VPHP 30-36 is equipped with a 3/4” con-
denser side drain stub in the front of the base pan.

Because of the unit’s unique draw-thru condenser
design, this drain stub must be connected to an
internal condensate removal system.

INDOOR MOTOR SPEED TAP SELECTION

WARNING

Before accessing the control compartment, discon-
nect power to the unit. Failure to do so could result
in serious injury or electrical shock.

For information on indoor motor speed tap selection,
please refer to the “VPAC/VPHP 30-36 Indoor Motor
Speed Tap Selection Chart” 

(Figure 4)

 and/or the la-

bel attached to the chassis of the unit.
The motor comes factory wired for the corresponding
units as described in the 230V column. Please make

speed tap changes as required by job site voltage and/
or external static pressure (e.s.p.) Speed tap changes
may need to be made from factory settings and Envi-

FIGURE 5 - RETURN AIR ACCESS PANEL

NOTE:

 Available with solid doors if separate intake is used.

Access

Panel

Frame

Frame

20” x 30”

Disposable

Filter

34”

60”

romaster International will not be liable for any sys-
tem problems that could arise if motor speed is not
changed to match application.

RETURN AIR ACCESS PANEL (WITH FILTER)

Return air access panels are unit capacity specific.
Be sure to specify unit capacity when placing an or-
der.
It is necessary to work closely with the other trades to
locate the opening for the return air access panel. The
return air access panel must be installed with enough
room available to remove the unit if necessary. The
frame is installed with screws through the lag holes
into the frame studs and should be level and plum.

(Figure 5)

 The return air access panel is set onto the

frame and held in place with six screws.

FINAL INSPECTION AND START UP

WARNING

Moving parts can cause injury so exercise caution
when testing the unit.

1. Hard wire line voltage power to unit. Refer to
unit rating plate for proper voltage and amperage/
fuse size.

NOTE:

 Some units may require two power sup-

plies (check nameplate and wiring diagram for fur-
ther instructions.)

FIGURE 4 - VPAC/VPHP 30-36 INDOOR MOTOR SPEED
TAP SELECTION CHART

Unit Size

ESP

230V

208V

197V

0.1

Blu

Blu

Blu

0.2

Blu

Blu

Blk

0.3

Blu

Blu

Blk

0.1

Blk

Blk

Blk

0.2

Blk

Blk

Blk

0.3

Blk

Blk

Blk

Tap Key -

 Blu (Med), Blk (High)

30

36

Содержание VPAC30

Страница 1: ...S Motors are thermally protected PSC type Air stream surfaces are insulated with 1 4 inch fiberglass or 1 8 inch volara The evaporator fan is a forward curved type directly mounted to the motor shaft...

Страница 2: ...uld result in serious injury or electrical shock All field wiring must be done in accordance to NEC and local codes Check the unit rating plate for circuit ampacity and breaker s or fuse size s Use on...

Страница 3: ...nd sound levels that a minimum clearance of 6 between the enclosure and the chassis be main tained It is also very important that the rough opening in the wall for the wall sleeve and louver be the co...

Страница 4: ...ressure e s p Speed tap changes may need to be made from factory settings and Envi FIGURE 5 RETURN AIR ACCESS PANEL NOTE Available with solid doors if separate intake is used Access Panel Frame Frame...

Страница 5: ...an limit the heat ing or cooling range of the thermostat A non mer cury electronic thermostat is available if needed Please contact the factory for more information SELECTING A COMPATIBLE THERMOSTAT W...

Страница 6: ...fan will continue to run to aid in the defrost process ELECTRIC HEAT OPERATION Place the thermostat system switch in heat mode Ad just the set point temperature above the room tem perature The electri...

Страница 7: ...connections Terminal ends that are loose will eventually fail causing a loss of performance or worse 5 Check fan motors and blower assemblies Some units may require a drop of light oil to motors and...

Страница 8: ...Max HACR Number Amps HP RLA LRA Amps HP Amps Voltage Breaker 30 208 230 60 1 1 7 0 25 14 73 3 0 5 18 7 197 22 3 35 36 208 230 60 1 1 7 0 25 16 3 88 3 0 5 21 197 25 1 40 VOLTS HZ PH M C A Condenser Fa...

Отзывы: