INSPECTION
Carefully check the shipment against the bill of lad-
ing. Make sure all chassis, wall sleeves, and louvers
(as well as any options) have been received. Inspect
each component for damage. The carrier must make
proper notation on the delivery receipt of all damage
identified and complete a carrier inspection report.
Concealed damage must be reported to the carrier
within 15 days of the receipt of the shipment.
IMPORTANT:
The purchaser must notify the EMI
traffic department of all damage and is responsible
for filing any necessary claims with the carrier.
APPLICATION LIMITATIONS
The VPAC/VPHP 30-36 should be installed in
accordance with all national and local safety codes.
Minimum and maximum operation conditions must be
observed to assure maximum system performance
with minimum service required. Refer to table below
for application limitations of the VPAC/VPHP 30-36.
CAUTION
Avoid possibility of electric shock and personal in-
jury. Disconnect all power before removing chas-
sis or performing any cleaning, servicing, or main-
tenance.
GENERAL INSTALLATION
Enviromaster International recommends installing the
VPAC/VPHP 30-36 before any carpentry work is
started for the enclosure. It is very important for proper
air flow and sound levels that a minimum clearance of
6” between the enclosure and the chassis be main-
tained. It is also very important that the rough opening
in the wall for the wall sleeve and louver be the cor-
rect dimension and in the exact position necessary
for installation.
(Figure 1)
The platform height should be the same level as the
bottom of the wall opening. Because wall sleeve
depths can vary depending on overall wall thickness,
it is critical that wall thickness be determined before
ordering the wall sleeve.
(Figure 2)
Consult factory
for available wall sleeve sizes.
1. Install 1/2” x 1/2” or 1” x 1” foam tape (supplied)
to the unit condenser top and sides to seal against
the wall sleeve.
(Figure 3)
FIGURE 3 - INSULATION & WEATHER ANGLES
Install supplied
1/2” x 1/2” foam
insulation along
top and sides of
condenser box.
(
I M P O R TANT:
Position as far
forward toward
outdoor side as
possible.)
Weather Angle
Position (One on
each side)
APPLICATION LIMITATIONS
Cool
Heat
115
75
DB/WB
DB
DB/WB
DB
Cool
Heat
Cool
Heat
67/57
50
90/72
80
Minimum
Maximum
Outdoor Ambient Air Temperature °F
Indoor Ambient Air Temperature °F
Cool
67
Minimum DB
Maximum DB
Exterior Wall
Wall Sleeve
Assembly
Cross Section
of Typical Wall
½” x ½” Foam Gasket
Overall Wall
Thickness
Wall Sleeve
Outdoor Louver
Drip edge will
extend outside
exterior wall
when installed
to guide con-
densate away
from building
Lag Holes
(4 Per Side)
Wall Sleeve Depth = Overall Wall
Thickness - 1.25” (Louver Depth)
FIGURE 2 - DETERMINING WALL SLEEVE DEPTH
Interior Wall