www.enviromaster.com
24
Multi-zone Heat Pump Condensing Units
T2HA DIMENSIONS AND SPECIFICATIONS
NOTE:
All EMI products are subject to ongoing development programs so design and
specifications may change without notice.
SOUND & WEIGHT DATA
Model
Sound Weight
dBA
Lbs.
T2HA8800
70
325
T2HA8400
70
325
T2HA4400
70
325
INTERCONNECTING TUBING SPECS
T2HA, T3HA, & T4HA models:
Nominal
Circuit
Capacity
Maximum
Length
Maximum
Lift
Liquid
Line
OD
Suction
Line
OD
9,000
100’
35’
1/4”
1/2”
12,000
100’
35’
1/4”
1/2”
18,000
100’
35’
3/8”
5/8”
24,000
100’
35’
3/8”
3/4”
T2HA, T3HA, AND T4HA - 208/230V - 60 HERTZ 1 - PHASE
CAPACITY
FAN MTR
COMPRESSOR
TOTAL
AMPS MCA
HACR
BRKR
MIN
VOLT
AMPS
HP
CIRCUIT #1
CIRCUIT #2
CIRCUIT #3
CIRCUIT #4
RLA LRA RLA LRA RLA LRA RLA
LRA
8800
1.8
0.33
5.4
36.0
5.4
36.0
-
-
-
-
12.6
14.0
15.0
197
4400
1.8
0.33
8.8
54.0
8.8
54.0
-
-
-
-
19.4
21.6
30.0
197
8400
1.8
0.33
5.4
36.0
8.8
54.0
-
-
-
-
16.0
18.2
25.0
197
Circuit Designators: 9 = 9000 Btuh 2 = 12000 Btuh 8 = 18000 Btuh 4 = 24000 Btuh
(ex. - 8400 consists of one 18000 Btuh
compressor and one 24000 Btuh compressor)
Содержание S2HA
Страница 2: ......