Multi-zone Heat Pump Condensing Units

The system will support refrigerant runs 

to the inside unit of up to 100' equivalent 

feet  with  a  35'  rise  included.  The  units 

are furnished with sweat connections and 

are  equipped  with  refrigerant  valves  and 

Schrader  fittings  for  charging  and  taking 

S2HA & T2HA REFRIGERANT PIPING INSTALLATION SECTION

• A P-trap is recommended when the suc-

tion riser is equal to or greater than 20 

feet in height.

• When the condenser is installed above 

the  evaporator,  the  P-trap  will  help  the 

return of oil back to the compressor.

• The placement of the P-trap should be at 

the  halfway  mark  of 

the  suction  riser.  For 

example  if  the  suc-

tion riser is 30 feet tall 

then a P-trap is recom-

mended at the 15 foot 

mark  of  the  suction 

riser

 

(see

 Figure #1

). 

• A P-trap may be fabri-

cated using; 

(2) street elbows and 

(2)  regular  elbows. A 

prefabricated  trap 

may be purchased 

from a Wholesaler or Distributor how-

ever  the  trap  should  be  shallow  as 

the: 

(4)  elbow  configuration.  Each  elbow  is 

approximately 2 equivalent feet. One 

P-trap  is  equal  to  approximately  8 

equivalent feet.

P-TRAP INSTALLATION

Figure #1

pressure readings. The following precau-

tions should be made:

•  Be  certain  no  burrs  remain  on  the 

fittings.

• Use only clean refrigeration tubing.
•  Use  tube  benders  to  guard  against 

kinking.

• Avoid  piping  on  wet  and  rainy  days 

and 

insulate suction line

. Be certain 

that plastic end caps remain in place 

when inserting through wall openings. 

Isolate tubing from transmitting vibra-

tion to the building or unit and avoid 

contact with sharp edges.

 Refrigera-

tion valves should be wrapped with 

a  wet  rag  "heat  sink"  to  protect 

valves while brazing. 

INTERCONNECTING TUBING SPECS 

S2HA, T2HA, T3HA, & T4HA models:

Nominal 

Circuit 

Capacity

Maximum 

Length

Maximum 

Lift

Liquid 

Line 

OD

Suction 

Line 

OD

9,000

100’

35’

1/4”

1/2”

12,000

100’

35’

1/4”

1/2”

18,000

100’

35’

3/8”

5/8”

24,000

100’

35’

3/8”

3/4”

NOTE: 

Refrigerant Piping Installation for both the S2HA & T2HA  models.

Содержание S2HA

Страница 1: ...1 1 04 07 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company S2HA Multi Zone S2HA T2HA HE...

Страница 2: ......

Страница 3: ...the electric supply to the unit The EMI America Series multi zone heat pump condenser must be con nected only to a properly grounded electrical supply Do not fail to prop erly ground this unit Turn of...

Страница 4: ...pad or foundation Refrigerant piping Disconnect switch SITE PREPARATION Place the unit on a at concrete surface or pad if on the ground Roof mounting should use a build up platform Piping is through...

Страница 5: ...allows for permanent mounting through the feet This is highly recommended due to the vertical design of the unit S2HA UNIT MOUNTING SECTION 5 Insert lag bolts through the holes in the bottom of the un...

Страница 6: ...within 3 feet of the unit 6 From the disconnect box run the power through the 7 8 hole on the side of the unit and into the electrical box and an chor with the strain relief tting 7 Run wires to the h...

Страница 7: ...east 18 awg 10 To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel 11 Tighten a...

Страница 8: ...irements 3 Use only HACR type breakers or time delay fuses Select the wire size accord ing to the ampacity rating Removethe four screws on the front panel 4 To access wiring diagram a Remove the four...

Страница 9: ...wires to the High Volt pigtail in the control box and attach L1 and L2 connections Also run green wire to ground lug T2HA INSTALLATION INSTRUCTIONS 8 Check wiring diagram for the required number of lo...

Страница 10: ...Wholesaler or Distributor how ever the trap should be shallow as the 4 elbow con guration Each elbow is approximately 2 equivalent feet One P trap is equal to approximately 8 equivalent feet P TRAP I...

Страница 11: ...ing and insert into ttings 7 Attach manifold set 3 The use of a shield is recommend one can be made from some scrap metal to protect the paint 4 Braze tubing into ttings S2C Shown S2HA T2HA REFRIGERAN...

Страница 12: ...he Refrig erant Charge Tables for proper weight charge and to the supplied Field Charging Charts for proper system pressures and temperature at different outdoor condi tions Superheat should be used f...

Страница 13: ...ning time between charge adjustments for the unit to stabilize The S T series S2HA T2HA T3HA T4HA has manifold access points on each of the service valves for the high and low pressures in cooling mo...

Страница 14: ...densing Units MULTI ZONE HEAT PUMP FIELD CHARGING Cooling Cycle 9 000 Btuh Circuit with EMI s WLHA09 or CAHB12 Note Minimum compressor superheat 5 F Cooling Cycle 12 000 Btuh Circuit with EMI s WLHA12...

Страница 15: ...ensing Units Cooling Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor superheat 5 F Cooling Cycle 24 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor s...

Страница 16: ...nviromaster com 16 Multi zone Heat Pump Condensing Units Heat Cycle 9 000 Btuh Circuit with EMI WLHA09 or CAHB12 Heat Cycle 12 000 Btuh Circuit with EMI WLHA12 or CAHB12 MULTI ZONE HEAT PUMP FIELD CHA...

Страница 17: ...romaster com 17 Multi zone Heat Pump Condensing Units MULTI ZONE HEAT PUMP FIELD CHARGING Heat Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Heat Cycle 24 000 Btuh Circuit with EMI s WLHA24 or...

Страница 18: ...ines occur on the 12 F superheat line 5 Add charge to obtain 12 F superheat Instructions 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gauge 2 M...

Страница 19: ...ci c to the unit being installed or call the factory Anti short cycle protection should be used on systems that use a conventional thermostat Evaporator Entering Air WB Evaporator Leaving Air DB Evapo...

Страница 20: ...located in the indoor unit provides 24V low Volt control power to the condenser outdoor unit This can be mea sured across low Volt terminals R and C Heat pump condensers utilize a reversing valve to p...

Страница 21: ...ibed in the manual pertaining to the indoor section The S Tseries S2HA T2HA T3HA T4HA will cease compressor operation at 35 F outdoor temperature If in heating mode the electric heat will take over wh...

Страница 22: ...230 60 1 1 8 0 33 4 3 27 4 3 27 10 4 11 5 15 9200 208 230 60 1 1 8 0 33 3 4 23 4 3 27 9 5 10 6 15 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh ex Model 9200 consists of one 9 000 Btuh compressor...

Страница 23: ...600 13 0 80 12 2 16 000 3 3 2200 WLHA12 WLHA12 22 600 13 0 72 11 9 20 000 3 3 9200 WLHA09 WLHA12 20 600 13 0 76 12 0 18 000 3 3 S2HA CAHB SYSTEM PERFORMANCE DATA MODEL COOLING HEATING S2HA Outdoor Ind...

Страница 24: ...Lift Liquid Line OD Suction Line OD 9 000 100 35 1 4 1 2 12 000 100 35 1 4 1 2 18 000 100 35 3 8 5 8 24 000 100 35 3 8 3 4 T2HA T3HA AND T4HA 208 230V 60 HERTZ 1 PHASE CAPACITY FAN MTR COMPRESSOR TOTA...

Страница 25: ...5 12 1 40500 3 2 CAHB T2HA SYSTEM PERFORMANCE DATA Model Cooling Heating T2HA Outdoor Condenser Indoor Air Handler Btuh SEER SHR EER Btuh COP 8800 CAHB24 CAHB24 36000 13 0 75 12 6 26400 3 1 8400 CAHB2...

Отзывы: