Multi-zone Heat Pump Condensing Units

MULTI-ZONE CONDENSER SEQUENCE OF OPERATION

EMI America Series multi-zone heat pump 

condensers  are  designed  to  operate  with 

EMI  America  Series  indoor  air  handlers. 

Both  the  condenser 

(outdoor  unit)

  and 

evaporator 

(indoor  unit)

  have  a  high  Volt 

service connection. Each is to be indepen-

dently  connected  to  the  electrical  service 

panel.

 (See the unit name plate for the cor-

rect  breaker  type  and  size)

.  The  outdoor 

and indoor units are also connected to each 

other through a low Volt interconnect wiring. 

A 24V transformer located in the indoor unit 

provides the low Volt power source. 

The S & T series (S2HA, T2HA, T3HA & 

T4HA) is a limited range heat pumps that 

will provide comfort cooling or heat pump 

operation operate at an outdoor tempera-

ture  range  between  35°F  and  115°F  for 

cooling,  35°F  and  75°F  for 

(heat  pump) 

heating.  The  outdoor  unit  is  equipped 

with  a  thermostat  that  will  switch  off  the 

condenser  when  temperature  falls  below 

35°F. For heat pump mode the condenser 

operation  will  cease  and  then  switch  on 

the indoor electric heat. For cooling mode, 

condenser operation will cease.

The S & T series (S2HA, T2HA, T3HA & 

T4HA) limited range heat pump condens-

ers  are  designed  to  operate  as  a  single 

stage cooling, two stage heating unit. For 

full operation the unit should be matched 

with  an  appropriate  EMI  indoor  unit  with 

electric heat and unit mounted controls or 

a wall mounted thermostat. 

For two stage heating operation the indoor 

unit must be equipped with an electric strip 

heater.

See the instruction manual for the indoor 

unit on the selection of the proper thermo-

stat for the system. 

Condenser Operation:

The  transformer  located  in  the  indoor  unit 

provides 24V, low-Volt control power to the 

condenser 

(outdoor unit)

. This can be mea-

sured across low-Volt terminals “R” and “C”.

Heat pump condensers utilize a reversing 

valve  to  provide  reverse  cycle  operation. 

Therefore  the  outdoor  unit  will  act  as  ei-

ther a condenser or an evaporator there-

by providing comfort cooling or heating to 

the  indoor  space.  The  reversing  valve  is 

energized in cooling. Should the valve fail 

to  actuate,  the  system  will  default  to  the 

heating mode of operation.

 

Cooling operation, Multi-zone Heat 

Pump:

Cooling mode operation requires that the 

control  (either  unit  mount  or  remote  wall 

mount thermostat) make a connection be-

tween low-Volt terminals “R” and “Y” along 

with “R” and “O”. When the indoor control 

is placed in cooling mode, with the set point 

temperature below the room temperature, 

the reversing valve will energize 

(R & O)

 

along with the compressor and outdoor fan 

(R & Y)

. When the indoor control is satis-

fied and the room temperature falls below 

the set temperature, the compressor and 

fan will de-energize. The EMI indoor unit 

is equipped with an anti-short cycle timer 

(ASCT)

 will prevent the compressor from 

re-starting for three minutes.

When the outdoor temperature falls below 

35°F, compressor operation will cease.

 Heating operation, Multi-zone Heat 

Pump:

Heating mode operation requires that the 

control  (either  unit  mount  or  remote  wall 

mount  thermostat)  make  a  connection 

between  low-Volt  terminals  “R”  and  “Y” 

only.  When  the  indoor  control  is  placed 

in  heating  mode,  with  the  set  point  tem-

perature  above  room  temperature,  the 

compressor and outdoor fan 

(R & Y)

 will 

energize. When the indoor control is satis-

fied and the room temperature rises above 

the set temperature, the compressor and 

fan will de-energize. The EMI indoor unit 

is equipped with an anti-short cycle timer 

(ASCT) 

will prevent the compressor from 

re-starting for three minutes.

Содержание S2HA

Страница 1: ...1 1 04 07 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company S2HA Multi Zone S2HA T2HA HE...

Страница 2: ......

Страница 3: ...the electric supply to the unit The EMI America Series multi zone heat pump condenser must be con nected only to a properly grounded electrical supply Do not fail to prop erly ground this unit Turn of...

Страница 4: ...pad or foundation Refrigerant piping Disconnect switch SITE PREPARATION Place the unit on a at concrete surface or pad if on the ground Roof mounting should use a build up platform Piping is through...

Страница 5: ...allows for permanent mounting through the feet This is highly recommended due to the vertical design of the unit S2HA UNIT MOUNTING SECTION 5 Insert lag bolts through the holes in the bottom of the un...

Страница 6: ...within 3 feet of the unit 6 From the disconnect box run the power through the 7 8 hole on the side of the unit and into the electrical box and an chor with the strain relief tting 7 Run wires to the h...

Страница 7: ...east 18 awg 10 To replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of the front panel covers the edge of the side panel 11 Tighten a...

Страница 8: ...irements 3 Use only HACR type breakers or time delay fuses Select the wire size accord ing to the ampacity rating Removethe four screws on the front panel 4 To access wiring diagram a Remove the four...

Страница 9: ...wires to the High Volt pigtail in the control box and attach L1 and L2 connections Also run green wire to ground lug T2HA INSTALLATION INSTRUCTIONS 8 Check wiring diagram for the required number of lo...

Страница 10: ...Wholesaler or Distributor how ever the trap should be shallow as the 4 elbow con guration Each elbow is approximately 2 equivalent feet One P trap is equal to approximately 8 equivalent feet P TRAP I...

Страница 11: ...ing and insert into ttings 7 Attach manifold set 3 The use of a shield is recommend one can be made from some scrap metal to protect the paint 4 Braze tubing into ttings S2C Shown S2HA T2HA REFRIGERAN...

Страница 12: ...he Refrig erant Charge Tables for proper weight charge and to the supplied Field Charging Charts for proper system pressures and temperature at different outdoor condi tions Superheat should be used f...

Страница 13: ...ning time between charge adjustments for the unit to stabilize The S T series S2HA T2HA T3HA T4HA has manifold access points on each of the service valves for the high and low pressures in cooling mo...

Страница 14: ...densing Units MULTI ZONE HEAT PUMP FIELD CHARGING Cooling Cycle 9 000 Btuh Circuit with EMI s WLHA09 or CAHB12 Note Minimum compressor superheat 5 F Cooling Cycle 12 000 Btuh Circuit with EMI s WLHA12...

Страница 15: ...ensing Units Cooling Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor superheat 5 F Cooling Cycle 24 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Note Minimum compressor s...

Страница 16: ...nviromaster com 16 Multi zone Heat Pump Condensing Units Heat Cycle 9 000 Btuh Circuit with EMI WLHA09 or CAHB12 Heat Cycle 12 000 Btuh Circuit with EMI WLHA12 or CAHB12 MULTI ZONE HEAT PUMP FIELD CHA...

Страница 17: ...romaster com 17 Multi zone Heat Pump Condensing Units MULTI ZONE HEAT PUMP FIELD CHARGING Heat Cycle 18 000 Btuh Circuit with EMI s WLHA24 or CAHB24 Heat Cycle 24 000 Btuh Circuit with EMI s WLHA24 or...

Страница 18: ...ines occur on the 12 F superheat line 5 Add charge to obtain 12 F superheat Instructions 1 Measure suction pressure and determine evaporator refrigerant temperature on R 22 scale of low side gauge 2 M...

Страница 19: ...ci c to the unit being installed or call the factory Anti short cycle protection should be used on systems that use a conventional thermostat Evaporator Entering Air WB Evaporator Leaving Air DB Evapo...

Страница 20: ...located in the indoor unit provides 24V low Volt control power to the condenser outdoor unit This can be mea sured across low Volt terminals R and C Heat pump condensers utilize a reversing valve to p...

Страница 21: ...ibed in the manual pertaining to the indoor section The S Tseries S2HA T2HA T3HA T4HA will cease compressor operation at 35 F outdoor temperature If in heating mode the electric heat will take over wh...

Страница 22: ...230 60 1 1 8 0 33 4 3 27 4 3 27 10 4 11 5 15 9200 208 230 60 1 1 8 0 33 3 4 23 4 3 27 9 5 10 6 15 1 Circuit Designators 9 9 000 Btuh 2 12 000 Btuh ex Model 9200 consists of one 9 000 Btuh compressor...

Страница 23: ...600 13 0 80 12 2 16 000 3 3 2200 WLHA12 WLHA12 22 600 13 0 72 11 9 20 000 3 3 9200 WLHA09 WLHA12 20 600 13 0 76 12 0 18 000 3 3 S2HA CAHB SYSTEM PERFORMANCE DATA MODEL COOLING HEATING S2HA Outdoor Ind...

Страница 24: ...Lift Liquid Line OD Suction Line OD 9 000 100 35 1 4 1 2 12 000 100 35 1 4 1 2 18 000 100 35 3 8 5 8 24 000 100 35 3 8 3 4 T2HA T3HA AND T4HA 208 230V 60 HERTZ 1 PHASE CAPACITY FAN MTR COMPRESSOR TOTA...

Страница 25: ...5 12 1 40500 3 2 CAHB T2HA SYSTEM PERFORMANCE DATA Model Cooling Heating T2HA Outdoor Condenser Indoor Air Handler Btuh SEER SHR EER Btuh COP 8800 CAHB24 CAHB24 36000 13 0 75 12 6 26400 3 1 8400 CAHB2...

Отзывы: