Electrical Wiring
Rating plate location
Figure 5
Rating
Rating
plate
plate
Remove side panel screws
Figure 6
NOTICE
All electrical wiring must be run accord-
ing to NEC and local codes.
1. Figure 5, Page 8 — Refer to the unit rat-
ing plate for voltage, minimum circuit
ampacity and over current protection
requirements.
Use only HACR type breakers or time
2.
delay fuses. Select the wire size according
to the ampacity rating.
To access electrical connections and wir-
3.
ing diagram:
a. Figure 6, Page 8 — Remove the
screws on the side panel that covers
the electrical box. Th
e box is adjacent
to the back panel and denoted with
electrical connections.
Th
e screws adjacent to the front panel
b.
should already be loose (don’t remove
them).
Slide the side panel out to access the
c.
high/low electrical connections and
wire diagram.
d. Figure 7, Page 9 —
Add
water-tight
strain relief fi tt ing to the high volt side
before wiring, a split grommet fi tt ing
has been factory installed in the low
volt side.
Power should be run to a weather proof
4.
disconnect box usually within 3 feet of
the unit.