background image

www.enviromaster.com

CAC Cassette Evaporator

4

CAC CASSETTE CONTROLS AND COMPONENTS

Continued

The cassette is best installed in new con-

struction or existing construction with a sus-

pended or false ceiling with enough clear-

ance to accommodate concealing the piping 

and electrical connections to the unit. 

PREPARATION FOR INSTALLATION

Unpacking:

  The  cassette  fascia  and 

main  chassis  are  packaged  together  for 

increased protection. 

• Remove the banding straps and lift the 

cardboard lid. 

•  Fascia  is  packed  in  bubble  wrap  and 

on top of the chassis (fascia is not at-

tached to the chassis for shipping).

•  Cardboard  template  is  between  the 

chassis and the fascia (

DO NOT

 throw 

template away with packaging!). 

• Lift the fascia and template from the box 

and set aside.

• Remove the Cassette chassis from the 

box  utilizing  the  four  corner  brackets 

for lifting. 

DO NOT 

use the drain or re-

frigerant connections for lifting.

• In order to protect the fascia from dirt 

and damage, it should be returned to 

the box until it is ready to be installed.

Blanking  off:

  When  branch  ducting 

is to be used, two polystyrene pieces for 

blanking off fascia openings are Included 

with the fascia packing. Up to two oppos-

ing sides may be blanked off.

DO  NOT 

throw  the  two  polystyrene 

blanking off pieces out with packaging!

Electromechanical  Operation  (Stan-

dard):

 An  optional  thermostat  can  be  ob-

tained through EMI or your local distributor.

NOTE:

 make sure the thermostat is 

suitable for unit operation (i.e., cool-

ing only, cooling/electric heat, etc.)

Filters:

 Metal framed filters are fitted. These 

are reusable and may be vacuum cleaned.

Condensate  pump:

  A  condensate 

pump  is  designed  to  carry  water  out  of 

the unit. The pump is fixed to a mounting 

bracket which can be withdrawn from the 

side  of  the  chassis  and  incorporates  an 

inspection hole to allow a visual check of 

the pump during operation. A float switch 

is  fitted  to  stop  the  cooling  action  (shut 

off the compressor) should the pump be-

come blocked or fail.

IMPORTANT:

 

Total lift for this pump is 

36” or less.

 

Air vanes:

 Air outlet vanes are manu-

ally  adjustable  on  the  9-12K  units  or 

driven  by  an  electric  motor  on  all  other 

model units. Where fitted, the motorized 

air vanes can be set to auto sweep or can 

be stopped in a fixed position.

Heating:

 The cassette may be fitted with  

electric  heaters  which  are  equipped  with 

over-temperature limit switches.

Fresh air connection:

 fresh air may be 

introduced to the unit by the addition of ducts 

connected to the fresh air knockouts on the 

Cassette case. It is usually advised that the 

fresh air volume is approximately 7-10% of 

the unit’s published maximum air flow.

Содержание CAC

Страница 1: ...6 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company CAC 9 12 Model Shown STRAIGHT COOL N...

Страница 2: ...ricaSeries evaporator must be connected only to a properly grounded electrical supply Do not fail to properly ground this unit Turn off the electrical supply before servicing the EMI AmericaSeries eva...

Страница 3: ...ire resistant thermal and acoustic foam insulation and light grey high impact ABS fascia A Styro foam drain pan with a tough re retardant thermoplastic liner Air Systems Fans are backward curved impel...

Страница 4: ...blanked off DO NOT throw the two polystyrene blanking off pieces out with packaging Electromechanical Operation Stan dard An optional thermostat can be ob tained through EMI or your local distributor...

Страница 5: ...e positioned in the fascia discharge slots to direct the air to the ducts Blanking Off Pieces Small Unit Shown Shown The large units have three hinged grills and three lters Medium Unit Shown Large Un...

Страница 6: ...the CAC Di mensions section in the back of this IOM for cabinet sizing Small Cabinet Dimension A 12 min Medium Cabinet DimensionA 11 min Large Cabinet Dimension A 13 min Dimension A 1 minimum space a...

Страница 7: ...iling will have to be cut to the following sizes Small cabinet 23 x 23 Medium cabinet 33 x 33 Large cabinet 46 x 33 NOTE Make sure the ceiling grid is supported separately from the Cas sette The ceili...

Страница 8: ...not pro trude more than 2 below the mounting bracket 2 MAX NOTE If the ceiling is not level or even it is important that the Cas sette is installed level to ensure cor rect pump operation and to main...

Страница 9: ...to the unit as possible This prevents a large volume of water draining back into the unit when it is switched off NOTE There is a check valve at the pump discharge to prevent water from draining back...

Страница 10: ...pes should be insulated right up to the Cassette chassis The CAC is equipped with a Flo Rater Piston Expansion device Connections are sweat type The suction line large must be insulated the entire len...

Страница 11: ...the bolts c Screw the mounting bolt with washer into the chassis leav ing approximately 1 to hang the fascia 4 On 18 36k units connect the vane motor plug by plugging it into the socket con nection on...

Страница 12: ...particularly in low Voltage wir ing The correct cable size must be used to ensure a Voltage drop of less than 1 Volt in the control wiring Once the refrigeration pipe work is complete the electrical...

Страница 13: ...onnector location terminal block L1 L2 Low Volt Interconnect Wiring Refer to the wiring diagram to connect the low Volt wiring to the appropriate terminals The wiring diagram located on the inside of...

Страница 14: ...f via the toggle switch on the side of the electri cal box Toggle Switch NOTE Apply power to the Condens ing Unit s crankcase heater for 24 hours before start up to boil off any liquid that may be pre...

Страница 15: ...re 4 ly with condensate pump energized If water does not check the pipe slope or see if there are any pipe restrictions 8 Ensure that all covers panels and l ters are in place and discharge louvers ar...

Страница 16: ...nds of tubing and insert into ttings 2 Protect the valves by wrapping with a wet rag heat sink before brazing 3 We recommend the use of a shield can be made from some scrap metal to protect the paint...

Страница 17: ...36 56 oz 90 oz R 22 8 Charge to proper weight charge based on your feet of interconnect see below NOTE Charging should be done with a dial a charge or weighed in with a scale TOP DISCHARGE REFRIGERANT...

Страница 18: ...at has been satis ed the purge feature al lows the indoor fan to remain on for an additional 60 seconds This increases ef ciency by pulling the remaining energy from the unit Cooling Operation The ele...

Страница 19: ...it Performance Data Date Model Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air...

Страница 20: ...r by sliding under retainer clips 5 Or use a garden hose Remove the grille and lter and hose off Let lter s and grille s dry before replacing Turn the POWER OFF to the unit be fore servicing or cleani...

Страница 21: ...tdoor unit are to be independently connected to the electri cal service panel and protected by sepa rate time delay fuse or HACR breakers See the unit name plate for the correct breaker type and size...

Страница 22: ...r condenser from short cycling After the thermostat is satis ed there will be a three minute delay before the condenser is allowed to re start Electric Heat Units with electric heat utilize a control...

Страница 23: ...sate pump with a high level safety switch If the condensate reaches a critical level or if power is lost to the indoor unit the safety cir cuit will open and low Volt power to the condenser terminal Y...

Страница 24: ...program all designs and speci cations are subject to change without notice INDOOR SOUND LEVELS dBa Model High Speed Medium Speed Low Speed 09 12 41 39 39 18 24 44 42 39 30 36 51 49 44 DISCHARGE AIR VO...

Страница 25: ...rator C D E F Control Box Small Cabinet CAC 9 000 12 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 2 1 x 2 C Condensate Discharge 1 D Suctio...

Страница 26: ...0 24 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 3 3 x 3 C Condensate Discharge 1 D Suction 1 E Liquid 1 F Condensate Pump Access 1 Contro...

Страница 27: ...36 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 3 3 x 3 C Condensate Discharge 1 D Suction 1 E Liquid 1 F Condensate Pump Access 1 B Contr...

Страница 28: ...74 22 7 197 28 3 30 S1C Side Discharge CAC CASSETTE SYSTEM MATCHES CAC CAC ELECTRICAL SPECIFICATIONS NOTE Due to EMI s ongoing product development program all designs and speci cations are subject to...

Страница 29: ...94 40 600 13 0 82 11 7 R22 CACA12 T3CA999 27 000 13 0 87 11 8 R22 CACA12 T3CA222 36 000 13 0 76 11 8 R22 CACA12 CACA24 T3CA928 39 000 13 0 80 11 7 R22 CACA12 CACA24 T3CA924 43 600 13 0 79 11 7 R22 CAC...

Страница 30: ...by others Failure to start due to Voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a conseq...

Страница 31: ...EFFICIENCY PRODUCT LINE EVAPORATORS CONDENSERS S1C S1H Single Zone Side Discharge S2C Dual Zone Side Discharge T2C T3C T4C 2 3 4 Zone Top Discharge WLC WLH High Wall Evaporator CAC Cassette Evaporato...

Страница 32: ......

Отзывы: