CAC Cassette Evaporator

22

Low Volt Controls

TROUBLESHOOTING PROCEDURE

 

Continued

Cooling Only Units:

Cooling only units require 18awg low Volt 

interconnecting wires between the indoor 

unit,  outdoor  units  and  thermostat.  Ter-

minals  designated  “Y1”  (yellow)  and  “C” 

(brown)  of  the  indoor  air  handler  should 

be  connected  to  the  corresponding  “Y” 

(yellow)  and  “C”  (brown)  wires  or  termi-

nals  of  the  outdoor  condenser.  Other 

wire(s) or terminals such as “R” (red) may 

not be needed and should be protect from 

making  contact  with  the  junction  box  or 

other metal surfaces.

Terminals “R”, “Y, “G”, “W” and “C” need 

to  connect  to  the  indoor,  wall  mounted 

thermostat.

NOTE:

 

“W” is required for units with 

electric  heat  only  “C”  may  not  be 

needed on some thermostats.

Refer  to  low  Volt  interconnect  diagram 

interconnect diagram figure 1 for remote 

thermostat connection.

A  24V  transformer  located  in  the  indoor 

air handler unit provides low Volt control 

power to both the indoor air handler and 

outdoor  condenser.  The  24v-power  sup-

ply can be measured by placing a meter 

across  the  “R”  and  “C”  low  Volt  termi-

nals  of  the  air  handler.  The  remote  wall 

mounted thermostat will switch on and off 

the condenser through the yellow (Y) and 

black (Y1) wires. When the thermostat is 

calling for cooling, 24V can be measured 

between terminals (wires) Y and C.

The indoor unit contains an electronic anti 

short cycle timer feature (ASCT) that will 

prevent the outdoor condenser from short 

cycling.  After  the  thermostat  is  satisfied 

there will be a three minute delay before 

the condenser is allowed to re-start.

Electric Heat:

Units  with  electric  heat  utilize  a  control 

relay  located  on  the  circuit  board  in  the 

control box. As a safety feature, an auto 

resetting limit switch located on the heat-

er  assembly  will  interrupt  power  to  the 

heater should an over-temperature condi-

tion occur. Each electric heat assembly is 

also equipped with a one time fuse link. 

Should  electric  heat  temperatures  rise 

above  the  auto  resetting  limit  switch,  a 

non-resetting, one time fuse link will open 

and the heater will remain off. If this oc-

curs the limit switch assembly must be re-

placed. Contact EMI technical service for 

a replacement.

The following current values apply when 

the  unit  is  connected  to  a  230V  power 

supply.  These  values  include  fan  motor 

current.  If  the  supply  power  is  different, 

this will in turn affect the amp draw of the 

heater.

5kw = 22.3 amps,    

3kw = 13.5 amps,    

1.5kw = 6.9 amps.

Units with Condensation Pumps:

EMI  CAC  is  equipped  with  an  internal 

condensate  pump  capable  of  removing 

condensate up to a three foot vertical lift. 

Condensation  generated  by  the  evapo-

rator  will  collect  in  the  pumps’  reservoir. 

When  the  water  level  is  high  enough,  a 

float  switch  will  close  and  energize  the 

pump  motor  clearing  the  water  from  the 

reservoir. Should, for any reason, the wa-

ter  exceed  the  maximum  preset  level,  a 

safety switch will open, there by interrupt-

ing the (Y1) signal to the condenser. This 

will prevent the evaporator from generat-

ing  additional  condensation  and  spilling 

out of the unit.

Содержание CAC

Страница 1: ...6 Enviromaster International LLC 5780 Success Dr Rome NY 13440 www enviromaster com INSTALLATION OPERATION AND MAINTENANCE MANUAL An ISO 9001 2000 Certi ed Company CAC 9 12 Model Shown STRAIGHT COOL N...

Страница 2: ...ricaSeries evaporator must be connected only to a properly grounded electrical supply Do not fail to properly ground this unit Turn off the electrical supply before servicing the EMI AmericaSeries eva...

Страница 3: ...ire resistant thermal and acoustic foam insulation and light grey high impact ABS fascia A Styro foam drain pan with a tough re retardant thermoplastic liner Air Systems Fans are backward curved impel...

Страница 4: ...blanked off DO NOT throw the two polystyrene blanking off pieces out with packaging Electromechanical Operation Stan dard An optional thermostat can be ob tained through EMI or your local distributor...

Страница 5: ...e positioned in the fascia discharge slots to direct the air to the ducts Blanking Off Pieces Small Unit Shown Shown The large units have three hinged grills and three lters Medium Unit Shown Large Un...

Страница 6: ...the CAC Di mensions section in the back of this IOM for cabinet sizing Small Cabinet Dimension A 12 min Medium Cabinet DimensionA 11 min Large Cabinet Dimension A 13 min Dimension A 1 minimum space a...

Страница 7: ...iling will have to be cut to the following sizes Small cabinet 23 x 23 Medium cabinet 33 x 33 Large cabinet 46 x 33 NOTE Make sure the ceiling grid is supported separately from the Cas sette The ceili...

Страница 8: ...not pro trude more than 2 below the mounting bracket 2 MAX NOTE If the ceiling is not level or even it is important that the Cas sette is installed level to ensure cor rect pump operation and to main...

Страница 9: ...to the unit as possible This prevents a large volume of water draining back into the unit when it is switched off NOTE There is a check valve at the pump discharge to prevent water from draining back...

Страница 10: ...pes should be insulated right up to the Cassette chassis The CAC is equipped with a Flo Rater Piston Expansion device Connections are sweat type The suction line large must be insulated the entire len...

Страница 11: ...the bolts c Screw the mounting bolt with washer into the chassis leav ing approximately 1 to hang the fascia 4 On 18 36k units connect the vane motor plug by plugging it into the socket con nection on...

Страница 12: ...particularly in low Voltage wir ing The correct cable size must be used to ensure a Voltage drop of less than 1 Volt in the control wiring Once the refrigeration pipe work is complete the electrical...

Страница 13: ...onnector location terminal block L1 L2 Low Volt Interconnect Wiring Refer to the wiring diagram to connect the low Volt wiring to the appropriate terminals The wiring diagram located on the inside of...

Страница 14: ...f via the toggle switch on the side of the electri cal box Toggle Switch NOTE Apply power to the Condens ing Unit s crankcase heater for 24 hours before start up to boil off any liquid that may be pre...

Страница 15: ...re 4 ly with condensate pump energized If water does not check the pipe slope or see if there are any pipe restrictions 8 Ensure that all covers panels and l ters are in place and discharge louvers ar...

Страница 16: ...nds of tubing and insert into ttings 2 Protect the valves by wrapping with a wet rag heat sink before brazing 3 We recommend the use of a shield can be made from some scrap metal to protect the paint...

Страница 17: ...36 56 oz 90 oz R 22 8 Charge to proper weight charge based on your feet of interconnect see below NOTE Charging should be done with a dial a charge or weighed in with a scale TOP DISCHARGE REFRIGERANT...

Страница 18: ...at has been satis ed the purge feature al lows the indoor fan to remain on for an additional 60 seconds This increases ef ciency by pulling the remaining energy from the unit Cooling Operation The ele...

Страница 19: ...it Performance Data Date Model Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air...

Страница 20: ...r by sliding under retainer clips 5 Or use a garden hose Remove the grille and lter and hose off Let lter s and grille s dry before replacing Turn the POWER OFF to the unit be fore servicing or cleani...

Страница 21: ...tdoor unit are to be independently connected to the electri cal service panel and protected by sepa rate time delay fuse or HACR breakers See the unit name plate for the correct breaker type and size...

Страница 22: ...r condenser from short cycling After the thermostat is satis ed there will be a three minute delay before the condenser is allowed to re start Electric Heat Units with electric heat utilize a control...

Страница 23: ...sate pump with a high level safety switch If the condensate reaches a critical level or if power is lost to the indoor unit the safety cir cuit will open and low Volt power to the condenser terminal Y...

Страница 24: ...program all designs and speci cations are subject to change without notice INDOOR SOUND LEVELS dBa Model High Speed Medium Speed Low Speed 09 12 41 39 39 18 24 44 42 39 30 36 51 49 44 DISCHARGE AIR VO...

Страница 25: ...rator C D E F Control Box Small Cabinet CAC 9 000 12 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 2 1 x 2 C Condensate Discharge 1 D Suctio...

Страница 26: ...0 24 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 3 3 x 3 C Condensate Discharge 1 D Suction 1 E Liquid 1 F Condensate Pump Access 1 Contro...

Страница 27: ...36 000 CAC CASSETTE DIMENSIONS FEATURE QTY SIZE A Optional Discharge Knockout 3 3 B Fresh Air Inlet Knockout 3 3 x 3 C Condensate Discharge 1 D Suction 1 E Liquid 1 F Condensate Pump Access 1 B Contr...

Страница 28: ...74 22 7 197 28 3 30 S1C Side Discharge CAC CASSETTE SYSTEM MATCHES CAC CAC ELECTRICAL SPECIFICATIONS NOTE Due to EMI s ongoing product development program all designs and speci cations are subject to...

Страница 29: ...94 40 600 13 0 82 11 7 R22 CACA12 T3CA999 27 000 13 0 87 11 8 R22 CACA12 T3CA222 36 000 13 0 76 11 8 R22 CACA12 CACA24 T3CA928 39 000 13 0 80 11 7 R22 CACA12 CACA24 T3CA924 43 600 13 0 79 11 7 R22 CAC...

Страница 30: ...by others Failure to start due to Voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs needed as a conseq...

Страница 31: ...EFFICIENCY PRODUCT LINE EVAPORATORS CONDENSERS S1C S1H Single Zone Side Discharge S2C Dual Zone Side Discharge T2C T3C T4C 2 3 4 Zone Top Discharge WLC WLH High Wall Evaporator CAC Cassette Evaporato...

Страница 32: ......

Отзывы: