NetSure
™
-48 VDC Power System
Installation Instructions, IM582127000100 (Revision A, January 9, 2017)
Spec. No: 582127000100, 582127000103
Document Code: IM582127000100
Model No: 7100
Revision A, January 9, 2017
[43]
Special Application Rectifier Bus Landing Point Kit P/N 563574
Special application rectifier bus landing point kit P/N 563574 is available for use with List 100 (582127000100) and List 103
(582127000103). Two (2) kits are required. When installed , the kits provide rectifier bus landing points for 350 kcmil cables. Refer to
Figure 28.
Special Application Rectifier Bus Landing Point Kit P/N 563574
GND RTN
Positive (+) Cable
-48V SUPPLY
Negative (-) Cable
Components removed in
illustration for clarity only.
Rear
P/N 563574
Hardware Buildup:
3/8-16 x 1-1/4” Bolt
3/8” Flat Washer
Lug
Busbar
3/8” Flat Washer
3/8” Lock Washer
3/8-16 Nut
Torque to 300 in-lbs.
Hardware Buildup:
3/8-16 x 1-1/4” Bolt
3/8” Flat Washer
Busbar
Busbar
3/8” Flat Washer
3/8” Lock Washer
3/8-16 Nut
Torque to 300 in-lbs.
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
StockCheck.com