5. 

INSTALLATION 

 

5.1  XWEB 

For installation, the XWEB system must not be open in any way. If the box is opened, the guarantee 
becomes void. Installation can take place in different ways depending on the model and the type of access to 
the user interf ace that you want to provide to the end user. The particularities of these types of connectivity 
are described in this manual. 
 
ATTENTION: in order to protect both yourself and the XWEB, the unit must be switched on only when all the 
electrical devices have already been connected. In order to avoid accidental switching on, ins ert the power 
cable only after connecting all the other external units. 
 

TERMINAL BLOCK 

26 

27 

 

Alarm Relay 1 (**) 

 

Power XWEB 

28 

29 

 

Alarm Relay 2 (**) 

33 

34 

 

External GSM modem power supply (*) 

30 

31 

32 

 

System Alarm Relay 

* 30-31 No Allarm 

* 30-32 Alarm 

 

 

 

USB port 

 

Ingresso digitale (**) 

 

 

COM port 

14 

15 

16 

 

RS485 A port 

 

 

 

RJ45 port 

17 

18 

19 

 

RS485B port (**)  

 

 

 

 

LED 

Led 

Colour 

Description 

Alarm 

Red 

RS485 alarm 

Rec 

Blue 

Data recording 

Power 

Green 

System turned on 

Status 

Green 

Messages are being sent 

System 

Red 

System alarm 

Alarm2 

Red 

Alarm relay 2 status (**) 

Alarm1 

Red 

Alarm relay 1 status (**) 

 

(*)= 12Vdc - 250mA. Compatible modem TC35-KIT (MC55i by Siemens, CINTERION L30960N2700A100),  

Gatetel GT-HE910-EUD,  Gatetel GT-HE910-NAD 

(**)= For XWEB 500DIN only 

 
 

Содержание XWEB300D

Страница 1: ...XWEB300D 500D PRO V 1 0 ...

Страница 2: ...NFIGURATION FOR XJA XJP XJM MODELS 11 6 REMOTE CONNECTIVITY 12 6 1 DESKTOP SOFTWARE REQUIREMENTS PC 12 6 2 SOFTWARE MOBILE REQUIREMENTS SMARTPHONE TABLET 12 6 3 CROSSOVER CABLE INSTRUCTIONS 13 6 4 INTRANET CONNECTIVITY OR LAN CONNECTION AND VPN 14 6 5 INTERNET CONNECTIVITY ON PUBLIC IP 15 6 6 WIFI CONNECTIVITY 16 7 EMERGENCY PROCEDURE 17 8 OPERATIVE PROCEDURES 19 9 SYSTEM IDENTIFICATION 19 10 TRAD...

Страница 3: ...resulting from the use of unsupported devices CAUTION Dixell srl reserves theright to amend this manual without prior notice The latest available version can be downloaded from the internet site CAUTION Immediately after the power failure no new data is recorded all recorded data is kept in non volatile memory The memory is electronic and no data is kept or conveyed to other media such as paper Wh...

Страница 4: ...ustomer s request and following a specific agreement Dixell s r l may be present during the start up of the final machine application as a consultant however under no circumstances canthe company be held responsible for the correct operation of the final equipment system CAUTION Since Dixell products form part of a very high level of technology a qualification configuration programming commissioni...

Страница 5: ...return the equipment to the distributor in case of purchase of a new one This equipment may contain hazardous substances improper use or incorrect disposal could have negative effects on human health and the environment The symbol shown on the product or on the packaging indicates that the product must be treated with separate waste In case of incorrect disposal sanctions can be applied as establi...

Страница 6: ...le female connector XWEB300 2x2 ways 1 green and 1 black 2x3 ways XWEB500 2x2 ways 2 greene 1 black 1x3 ways 1x7 ways 1 Jumper 2 vie If one of the following parts is damaged promptly contact your dealer You may also receive a modem or a wifi dongle which will not be included in the same p ackage as a package option When working with a modem connection always check that the type of modem you are ab...

Страница 7: ...e loads AUX1 port Systema Alarm in exchange connectable via 3 way terminal block always present AUX2 Alarm 1 and AUX3 Alarm 2 ports that can be connected via a 2 way terminal block present only for XWEB500D Pwr Ext Modem clean contacts 12Vdc max 250mA connectable via 2 way terminal block always present RS485 Ports RS485 port 1 optically isolated always present RS485 port 2 optically isolated only ...

Страница 8: ...already been connected In order to avoid accidental switching on insert the power cable only after connecting all the other external units TERMINAL BLOCK 26 27 Alarm Relay 1 1 2 Power XWEB 28 29 Alarm Relay 2 33 34 External GSM modem power supply 30 31 32 System Alarm Relay 30 31 No Allarm 30 32 Alarm USB port 6 7 Ingresso digitale COM port 14 15 16 RS485 A port RJ45 port 17 18 19 RS485B port LED ...

Страница 9: ...the service It is necessary to insert this relay in the power supply circuit of the external modem to ensure the correct sending of messages SMS ATTENTION During the initial start up phase the STATUS REC and ALARM LEDs FLASH at regular intervals This flashing IS NORMAL and highlights the regular progress of the ignition phase which can last up to 5 minutes Avoid direct passage between operators as...

Страница 10: ...t 485 which must be respected when connecting the instruments to the network Below is a list of operating tips to obtain the best result in terms of instrument net work reliability RS485 serial connection The serial line cable can be of the two wire type plus the shield with a minimum section of 0 5mm2 eg BELDEN 8772 This cable is recommended for its technical characteristics and for maintaining t...

Страница 11: ...he RS485 line balanced the ends must be terminated with a 1500Ω resistor If the XWEB is at one end of the RS485 line it is advisable to insert the 120Ω termination resistor on the last instrument and on the XWEB To activate the EOL resistor insert enable TERM DO NOT enable it if the XWEB is in the middle of the RS485 line 5 3 CONFIGURATION FOR XC400 600 800 900 AND XH200 300 400 SERIES These instr...

Страница 12: ...PHONE TABLET Browser Support Minimum Version Apple iOS Safari SUPPORTED 10 3 Android Google Chrome SUPPORTED 58 Android MozillaFirefox SUPPORTED 54 All newer computers are capable of meeting these requirements However it is advisable to use the advice of a computer expert to evaluate the computers to be purchased and or already in your possession In the following sections general information on po...

Страница 13: ...address bar Displaying the initial page login will complete the connection procedure Enter username and password to start using your XWEB Warning a prerequisite to be able to connect correctly is the compatibility of the IP class between the XWEB address and that of the network interface of your PC For example with theXWEB network interface configured at 192 168 0 200 the network interface of your...

Страница 14: ...e for your PC any software and credentials if you want to use a VPN network for access Before connecting the XWEB to the network check that the IP address you wish to use for the XWEB is actually free and therefore usable You could perform a PING to that address and if at least one reply is received at the PING the address must be changed as it is already used Example Before connecting the XWEB to...

Страница 15: ...ifically requested from your ISP Internet Service Provider Tell your ISP that you want to install a webserver this will help them recognize your needs and provideyou with an adequate connection It is highly recommended to obtainall the details of the supply contract for the management of any future connection problems Connection to the internet is possible in the presence of a router Its configura...

Страница 16: ...e XWEB access point XWEB is normally supplied preconfigured in this mode so that the user can search with his PC smartphone tablet to an XWEB EVO SSID network The default password is dixellxwebpro i Connection of XWEB to existing wifi network XWEB can be connected via wifi to a Wifi AccessPoint already present on the site In this case you need to temporarily access the xweb interface with another ...

Страница 17: ... address 192 168 0 6 or compatible class 4 Power on XWEB and wait a couple of minutes 5 Open with your browser Firefox or Chome the address http 192 168 0 150 A page like the one below will be presented in which will be present a MAC Address XWEB alphanumeric identification code b IP Address IP address functioning outside theemergency procedure c HTTP HTTPS Port web service ports operating outside...

Страница 18: ...onfiguration parameters the system will then be reachable outside the emergency procedure with the IP of IP ADDRESS present on the page described in the previous section 7 Open the JMP contacts by disconnecting the jumper 8 Enter the credentials provided by Dixell Technical Support the data of MAC ADDRESS and DATE must be provided beforehand 9 Press the Confirm key if the data entered are correct ...

Страница 19: ...___________________ example 8 8 8 8 SMTP ___________________________ example 192 168 0 14 E mail Address ___________________________ example myXWEB001 company com Telephone number ___________________________ 10 TRADEMARKS Consider It Solved and Intelligent Store are trademarks and Emerson Climate Technologies and the Emerson Climate Technologies logo are service marks and trademarks of Emerson Ele...

Страница 20: ..._________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ __________________________________________...

Отзывы: