1592023140 XM678D GB r2.8  01.09.2017.docx 

XM678D  

          10/

15

 

 

 

LABEL 

VALUE 

DESCRIPTION 

RANGE 

NOTES 

 

FtY 

404 

Kind of gas. 

Type of gas used by plant.  

Fundamental parameter for correct functioning of all system

LABEL

 

REFRIGERANT 

OPERATING RANGE  

R22  

 r22  

-50-60°C/-58÷120°F 

134  

r134A 

-50-60°C/-58÷120°F 

290  

r290 – Propane 

-50-60°C/-58÷120°F 

404  

r404A 

-70-60°C/-94÷120°F 

47A 

r407A 

-50-60°C/-58÷120°F 

47C 

r407C 

-50-60°C/-58÷120°F 

47F  

r407F 

-50-60°C/-58÷120°F 

410  

r410A 

-50-60°C/-58÷120°F 

448 

r448A 

-45-60°C/-69÷120°F 

449 

r449A 

-45-60°C/-69÷120°F 

450 

r450A 

-45-60°C/-69÷120°F 

507  

r507 

-70-60°C/-94÷120°F 

513 

r513A 

-45-60°C/-69÷120°F 

CO2 

r744  - Co2 

-50-60°C/-58÷120°F 

 

 

Atu 

Minimum STABLE superheat search 

No; yES 

This  parameter  enables  the  search  of  the  minimum  stable 
superheat. The lowest admitted value is LSH+2°C 

 

AMS 

Self self adaptive SH regulation enabling 

No; yES 

This  parameter  enables  the  self  adaptive  regulation  of  the 
superheat. CrE = no must to be set, when this function is enabled. 

 

SSH 

8.0 

Superheat set point. 

[0.1°C to 25.5°C] 

[1°F to 45°F] 

This is the value used to regulate superheat. 

 

Pb 

8,0 

Proportional band. 

[0.1°C to 60.0°C] 

 [1°F to 108°F] 

The valve changes its opening on the band 

[SSH

SSH + Pb]

. At 

SSH

  value  of  superheat  the  valve  will  be  at  0%  (without  integral 

contribution) and at 

[SSH + Pb]

  value of superheat the  valve will 

be  at 

MnF

.  For  values  bigger  than 

[SSH  +  Pb]

  the  valve  is 

completely opened. 

 

rS 

0.0 

Proportional band reset 

[-12.0°C to 12.0°C] 

It allows to move the regulation band, above or below the  SH set 
point. 

 

inC 

200 

Integration time for superheat regulation. 

 0 to 255s 

 

PEO 

50 

Valve  opening  in  case  of  error  on  probes 
P5 or P6. 

0 to 100% 

If a temporary probe error occurs, valve opening percentage is 

PEo 

until 

PEd 

time is elapsed. 

 

OPE 

85 

Start opening percentage for the time 

SFd

It’s not limited by the MnF parameter

 

0 to 100% 

Opening valve percentage when start function is active. This phase 
duration is 

SFd 

time. 

 

SFd 

0.1 

Duration of soft start phase with opening at 

OPE

0.0 to 42min00sec (252) 

Set start function duration and post-defrost duration. 

During this 

phase the alarms are neglected.  
Format

: min.10sec, 

resolution

: 10sec. 

 

OPd 

85 

Valve opening percentage  during hot gas 
defrost. 

It’s  not  limited  by  the  MnF 

parameter.

 

0 to 100% 

Opening  valve  percentage  during  hot  gas  defrost.  During  hot  gs 
defrost there is not SH control. 

 

MnF 

100 

Maximum percentage of opening admitted 
(during normal functioning). 

0 to 100% 

During regulation it sets the maximum valve opening percentage. 

This  value  is  not used  during  the  SFd phase  (soft  start)  and 
during hot gas defrost, where the fixed percentace of the valve 
opening is set by oPd.

 

 

Fot 

nU 

Manual opening. 

0 to 100% 

nU 

It  permits  to  force  the  valve  opening  to  the  specified  value.  This 
value overwrites the one calculated by PID algorithm.  

!!!! WARNING !!!! 
It must be [Fot = nU] to have correct superheat regulation.

 

 

PA4 

-0.5 

Probe value at 4mA or at 0V. 

Meas 
Unit 

Range 

BAR 

[PrU=rE] -1.0 to P20 
[PrU=Ab]  0.0 to P20 

PSI 

[PrU=rE]  -14 to P20 
[PrU=Ab]    0 to P20 

dKP 

[PrU=rE]  -10 to P20 
[PrU=Ab]    0 to P20 

 

Value of pressure at 4mA for current probe [4 to 20mA] or value at 
0V  for  ratiometric  probes.  The  value  is  absolute  or  relative 
according to 

PrU

 parameter. 

 

P20 

11.0 

Probe value at 20mA or at 5V. 

Meas 
Unit 

Range 

BAR 

[PrU=rE] PA4 to 60.0 
[PrU=Ab] PA4 to 60.0 

PSI 

[PrU=rE] PA4 to 870 
[PrU=Ab] PA4 to 870 

dKP 

[PrU=rE] PA4 to 600 
[PrU=Ab] PA4 to 600 

 

Value of pressure at 20mA for current probe [4 to 20mA] or value 
at  5V  for  ratiometric  probes.  The  value  is  absolute  or  relative 
according to 

PrU

 parameter. 

 

LPL 

-0.5 

Lower  Pressure  Limit  for  superheat 
regulation. 

PA4 to P20 

EXPERT:

 when suction pressure goes down the lower bound 

LPL, 

superheat

 

regulation will use a fixed pressure value. Otherwise, the 

normal pressure value will be used (according to 

PrU 

parameter). 

 

MOP 

11.0 

Maximum  operating  pressure  threshold 
and valve closing of 

dML

 value. 

LOP to P20 

If  suction  pressure  exceeds  maximum  operating  pressure  value, 
the  instrument  will  signal  this  situation  giving  the 

MOP

  alarm 

(according to 

PrU

 parameter). 

 

LOP 

-0.5 

Minimum  operating  pressure  threshold 
and valve opening of 

dML

 value. 

PA4 to MOP 

If suction pressure exceeds minimum operating pressure value, the 
instrument will signal this situation giving the 

LOP

 alarm (according 

to 

PrU

 parameter). 

 

dML 

30 

Delta 

[MOP - LOP].

 

0 to 100% 

Until 

MOP

 alarm is active, the valve will close, every second, of a 

value equal to the 

dML

 percentage. 

Until 

LOP

 alarm is active, the  valve will open, every second, of a 

value equal to the 

dML

 percentage. 

 

MSH 

60.0 

Maximum superheat alarm threshold. 

 [LSH to 80.0°C] 

[LSH to 144°F] 

If  superheat  value  exceeds 

MSH

  value,  the  display  will  show  the 

MSH

 message until delay time 

SHd

 will expire. 

Содержание XM678D

Страница 1: ... that permits to be programmed in a simple way The optional direct serial output RS485 ModBUS compatible permits a simple XWEB interfacing RTC is available as options The HOT KEY connector can be used to connect X REP display Depending on the model 4 QUICK REFERENCE GUIDE HOW TO RUN THE SELF ADAPTIVE REGULATION IN 5 STEPS 1 After wiring the XM678D configure the type of valve bipolar or unipolar vi...

Страница 2: ... wrong settings tEP Model LSt steps 10 uSt steps 10 CPP mA 10 CHd mA 10 Sr step s tEu bip unip HSF Half full 0 Manual settings Par Par Par Par Par Par Par 1 Danfoss ETS 25 50 7 262 10 10 300 bP FUL 2 Danfoss ETS 100 10 353 10 10 300 bP FUL tEP Model LSt steps 10 uSt steps 10 CPP mA 10 CHd mA 10 Sr step s tEu bip unip HSF Half full 3 Danfoss ETS 250 400 11 381 10 10 300 bP FUL 4 Sporlan SEI 5 to 11...

Страница 3: ...the bounds of the pressure transducer or the P5C parameter is wrong Check all these options and eventually change the transducer rPF the remote pressure transducer is on error situation Check the status of the onboard GREEN LED if this LED is OFF the LAN is not working otherwise check the remote transducer LAST CHECKS ABOUT SUPERHEAT On the fast access menu dPP is the value read by the pressure ga...

Страница 4: ...ow the air temperature set is sufficient to press and release the SET button the value is displayed for about 60 sec 9 HOW TO PROGRAM THE PARAMETERS PR1 AND PR2 The device provide 2 programming levels Pr1 with direct access and Pr2 protected with a password intended for experts ACCESS to Pr1 Press and hold for about 3 sec to have access to the first programming level Pr1 Select item or Select the ...

Страница 5: ...can perform simultaneous defrosts with the possibility to end them in a synchronized way The Adr parameter cannot be duplicated because in this case the defrost cannot be correctly managed BEGIN Press for 3 seconds the rtC or other will be showed The measurement unit blinks Find Adr Press more than once the DOWN arrow to find the Adr parameter the press SET Modify Adr or Set the value of Adr param...

Страница 6: ...h racks Sub 5 13 2 GENERAL CONSIDERATIONS The controller is able to regulate the superheat in manual or self adaptive mode according to the value of the parameter AMS autotuing enabling With AMS n the normal SH regulation is performed With AMS y the self adaptive SH regulation is performed 13 3 MANUAL OPERATING MODE AMS NO The temperature and SH regulation can be performed in 2 ways according to t...

Страница 7: ... physical probe or virtual probe obtained by a weighted average between two probes following the formula value_for_room_regulation rPA rPE rPb 100 rPE 100 If the temperature increases and reaches set point plus differential the solenoid valve is opened and then it is closed when the temperature reaches the set point value again In case of fault in the thermostat probe the opening and closing time ...

Страница 8: ...o that the relay will be ON for AMt minutes and OFF for 60 AMt minutes In case of P4 error or if P4 is absent the output is at AMA value for the AMt time then the output is at 0 value for the time 255 AMt time performing a simple PWM modulation 16 6 AUXILIARY OUTPUT The auxiliary output is switch ON and OFF by means of the corresponding digital input or by pressing and releasing the down arrow key...

Страница 9: ...0 during workdays nU not used Format hours 10min resolution 10min Ld2 13 0 Workdays Second defrost start Ld1 to 23h50min 143 nU 144 Ld3 21 0 Workdays Third defrost start Ld2 to 23h50min 143 nU 144 Ld4 nU Workdays Fourth defrost start Ld3 to 23h50min 143 nU 144 Ld5 nU Workdays Fifth defrost start Ld4 to 23h50min 143 nU 144 Ld6 nU Workdays Sixth defrost start Ld5 to 23h50min 143 nU 144 Sd1 6 0 Holid...

Страница 10: ...pening valve percentage during hot gas defrost During hot gs defrost there is not SH control MnF 100 Maximum percentage of opening admitted during normal functioning 0 to 100 During regulation it sets the maximum valve opening percentage This value is not used during the SFd phase soft start and during hot gas defrost where the fixed percentace of the valve opening is set by oPd Fot nU Manual open...

Страница 11: ... closer of the valve and then will restart working REGULATION SET 5 0 Set point LS US Target set point for temperature regulation HY 2 Differential 0 1 C to 25 5 C 1 F to 45 F If CrE n then HY is the hysteresis for ON OFF thermoregulation If CrE Y or CrE EUP then HY is the proportional band for temperature PI controller On these cases the value should be greater than 5 C int 150 Integral time for ...

Страница 12: ...evaporator probe is present idF 6 Defrost interval 0 to 120hours It sets the time interval between the beginning of two defrost cycles EdF in it is the interval between 2 defrost EdF rtC it is the safety interval in case of clock alarm RtC RtF idF 0 the defrost can be activated only manually or through RS485 or from external contact or from LAN MdF 45 Maximum duration for defrost 0 to 255min When ...

Страница 13: ... reached and the ALd delay time is expired the LA alarm will be enabled AHY 1 0 Differential for room temperature alarm 0 1 C to 25 5 C 1 F to 45 F Threshold recovery after a temperature alarm ALd 15 Room Temperature alarm delay 0 to 255min Time interval between the detection of an alarm condition and the corresponding alarm signaling dLU 150 High temperature alarm detected by defrost probe dLL 15...

Страница 14: ...P CL Digital input 3 polarity OP CL CL means the digital input is activated by closing the contact OP means the digital input is activated by opening the contact i3F ES Digital input 3 configuration EAL bAL PAL dor dEF AUS LiG OnF Htr FHU ES HdY EAL external alarm bAL serious external alarm PAL pressure switch activation dor door open dEF defrost activation AUS auxiliary activation LiG light activ...

Страница 15: ...C ntC P1 configuration nP PtC ntC CtC PtM nP not present PtC Ptc ntC ntc CtC ntc US PtM Pt1000 Ot 0 P1 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the thermostat probe P2C ntC P2 configuration nP PtC ntC CtC PtM nP not present PtC Ptc ntC ntc CtC ntc US PtM Pt1000 oE 0 P2 calibration 12 0 C to 12 0 C Allows to adjust possible offset of the evaporator probe P3C nP P3 configurat...

Отзывы: