Auxiliary Output
Parameters List • 19
SERVICE - READ ONLY
CLt
Cooling time percentage: it shows the effective cooling time calculated by XM600 during regulation
tMd
Time to next defrost: it shows time before the next defrost if interval defrost is selected
LSn
L.A.N. section number (1 to 5) Shows the number of sections available in the L.A.N.
Lan
L.A.N. serial address (1 to LSn) Identifies the device address inside local network of multiplexed cabinet
controller.
Adr
RS485 serial address (1 to 247): Identifies the device address when connected to a MODBUS compatible
monitoring system.
Rel
Release software: (read only) Software version of the microprocessor.
Ptb
Parameter table: (read only) it shows the original code of the dIXEL parameter map.
Pr2
Access to the protected parameter list (read only)
Table 8-1 - XM670 to XM679 Parameters List