13
Compressor Operation with VFD Drive
Start
Compressor
Start VFD at
Minimum Speed
(30 Hz Typ.)
Is Control Press.
Within Setpt
Deadbands?
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Is Capslide @
100%
Increase or Decrease the
Compressor Capacity Slides to
Match Setpoints
Increase or Decrease Motor Speed
@ Rate Defined by VFD PID
Parameters
Is Control Press @
Setpoint?
Is Motor Speed @
Min?
No
Yes
No
Yes
No
No
Check/Adjust Capacity Slide
Check/Adjust VFD
Yes