Motor Speed Setpoints & Control Screen
VFD SCREEN SETTINGS
Settings:
Auto Button:
Choosing Auto will do the following:
1.
While the fan is off the
Output Mode
will be forced to
Manual Mode
.
2.
When the fan starts, it will remain in
Manual Mode
at the
Initial Speed
for the period defined as
Delay Auto.
3.
After the
Delay Auto
time expires, the
Output Mode
will change to
Auto Mode.
4.
In
Auto Mode
, the VFD is enabled to increase and decrease speed to maintain the temperature set-
tings.
5.
Increase At:
High setting where an increase of speed is desired.
6.
Decrease At:
Low setting where a decrease of speed is desired
7.
Initial Speed:
Desired forced speed to start the fan at as described above. Note: The PLC will auto-
matically keep this value to at least the
Minimum Speed
setting.
Содержание VSG & VSSG
Страница 1: ...1 VSG VSSG Single Screw Compressor Software Manual Compact Logix PLC ...
Страница 2: ...2 ...
Страница 4: ...4 ...
Страница 14: ...14 ...
Страница 21: ...21 Discharge Pressure Control There are three options for the Compressor Control Setpoints ...
Страница 22: ...22 Suction Pressure Control ...
Страница 23: ...23 Process Temperature Control ...
Страница 39: ...39 Instrument Calibration ...
Страница 46: ...46 ...
Страница 67: ...67 Captured Data at Shutdown The Captured at Shutdown screen shows data captured prior to compressor shutdown ...
Страница 68: ...68 ...
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......
Страница 79: ......
Страница 81: ......
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ...69 ...