Section 3: Mounting and Connection
April 2013
Mounting and Connection
3.4.5
Power
The Gateway is designed to be powered by 24 VDC (nominal) and requires 250 mA of current.
The positive and negative connections are found on the left side of the terminal block
(
Figure 3-6
). An additional case ground is found on the left side of the junction box enclosure.
Connect supply power to the po and negative – power terminals found on the left side of
the terminal block (
Figure 3-6
). Recommended torque is 7 in-lbs and the gauge is 12 to 22 AWG.
An additional internal case ground can be found on the left side of the enclosure. The wiring
should include an external power shut-off switch or circuit breaker that is located near the
Gateway.
Note
Using an uninterruptible power supply (UPS) is recommended to ensure availability should there
be a loss of power.
Содержание Smart Wireless Gateway
Страница 1: ...Reference Manual 00809 0200 4420 Rev GA April 2013 Smart Wireless Gateway ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0200 4420 Rev GA Title Page April 2013 ...
Страница 8: ...4 Reference Manual 00809 0200 4420 Rev GA Table of Contents April 2013 Table of Contents ...
Страница 22: ...14 Reference Manual 00809 0200 4420 Rev GA Section 2 Initial Connection April 2013 Initial Connection ...
Страница 58: ...50 Reference Manual 00809 0200 4420 Rev GA Section 6 Troubleshooting April 2013 Troubleshooting ...
Страница 74: ...66 Reference Manual 00809 0200 4420 Rev GA Appendix B Product certifications April 2013 Product certifications ...
Страница 80: ...72 Reference Manual 00809 0200 4420 Rev GA Appendix C DeltaV ready April 2013 ...
Страница 90: ...82 Reference Manual 00809 0200 4420 Rev GA Appendix D Redundancy April 2013 ...
Страница 91: ......