40
Reference Manual
00809-0200-4420, Rev GA
Section 5: Host Integration
April 2013
Host Integration
Table 5-1. Device parameters available
PV, SV, TV, and QV (dynamic variables) will vary by device type. Please refer to the device’s
documentation for more information on what value is represented by each dynamic variable.
RELIABILITY and ONLINE relate to wireless communications. RELIABILITY is the percentage of
messages received from the wireless field device. ONLINE is a true/false indication of whether
the device is communicating on the wireless network.
**_HEALTHY parameters are a true/false indication of the health of a particular variable (** =
dynamic variable – PV, SV, etc…). These parameters incorporate critical diagnostics from the
wireless field device as well as communication status.
Note
The **_HEALTHY parameters are a great indication of the health and communications status of
the data values.
State (state value): The value of a data point which drives a Modbus output of 1. For example, if a
data point is reported as either True or False, a state value of True will report a 1 for True and 0 for
False. A state of False will report a 0 for True and a 1 for False. State is only required for register
numbers 0-19999 (Boolean, bit, coil, binary, etc…).
Invert: This check box will invert the Modbus output from a 1 to a 0 or a 0 to a 1. Invert is only
used for Boolean values using register numbers 0-19999.
Gain: This value is multiplied to the data value for the purpose of scaling integers. Gain is only
required if scaled is chosen on the Modbus communications page and globe gain and offset is
not chosen.
Offset: This value is added to the data value for the purpose of scaling integers. Offset is only
required if scaled is chosen on the Modbus communications page and globe gain and offset is
not chosen.
Parameter
Description
Data Type
PV
Primary Variable
32 bit float
SV
Secondary Variable
32 bit float
TV
Tertiary Variable
32 bit float
QV
Quaternary Variable
32 bit float
RELIABILITY
A measure of connectivity to the
Gateway
32 bit float
ONLINE
Wireless communications status
Boolean
PV_HEALTHY
Health status for PV
Boolean
SV_HEALTHY
Health status for SV
Boolean
TV_HEALTHY
Health status for TV
Boolean
QV_HEALTHY
Health status for QV
Boolean
Содержание Smart Wireless Gateway
Страница 1: ...Reference Manual 00809 0200 4420 Rev GA April 2013 Smart Wireless Gateway ...
Страница 2: ......
Страница 4: ...iv Reference Manual 00809 0200 4420 Rev GA Title Page April 2013 ...
Страница 8: ...4 Reference Manual 00809 0200 4420 Rev GA Table of Contents April 2013 Table of Contents ...
Страница 22: ...14 Reference Manual 00809 0200 4420 Rev GA Section 2 Initial Connection April 2013 Initial Connection ...
Страница 58: ...50 Reference Manual 00809 0200 4420 Rev GA Section 6 Troubleshooting April 2013 Troubleshooting ...
Страница 74: ...66 Reference Manual 00809 0200 4420 Rev GA Appendix B Product certifications April 2013 Product certifications ...
Страница 80: ...72 Reference Manual 00809 0200 4420 Rev GA Appendix C DeltaV ready April 2013 ...
Страница 90: ...82 Reference Manual 00809 0200 4420 Rev GA Appendix D Redundancy April 2013 ...
Страница 91: ......