Initial Connection
2.3.3
Configure the gateway
It is now possible to log into the Gateway for the first time and begin configuration for
placement on a live control network. The following items need to be configured:
Security Passwords
Time Settings
TCP/IP Network Settings
Use the following procedure to log in to the Gateway:
1.
Open a standard web browser.
2.
Enter
https://192.168.1.10
in the address bar.
3.
Continue though the security message.
4.
Enter
admin
for User Name.
5.
Enter
default
for the Password.
The web browser will now be directed to the Gateway’s default home page. There is a navigation
menu located on the left hand side with four main areas.
Diagnostics: View status of communications, client server parameters, and more
Monitor: Screens created by the user to view data from field devices
Explorer: Basic view of values from field devices
Setup: Configure the Gateway for operations, security, and host system integration
Security passwords
There are four role based user accounts for the Gateway with varying levels of access.
Table 2-2
below describes this access.
Table 2-2. Role Based Access User Accounts
Role
User name
Web interface access
Executive
exec
Read-only access
Operator
oper
Read-only access
Maintenance
maint
Configure HART
®
device settings
Configure Modbus communications
Configure Modbus register mapping
Configure OPC browse tree
Configure Active Advertising
Administrator
admin
Includes all maintenance privileges
Configure Ethernet network settings
Configure WirelessHART network settings
Set passwords
Set time settings
Set home page options
Configure custom point pages