1.  End connections threaded to other than ASME standards can usually be supplied.

2.  The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.

Specifications

Body Size and End Connection Styles

(1)

NPS 3/4 or 1, NPT

Maximum Operating inlet Pressure

(2)

125 psig (8,6 bar)                  

Maximum allowable Emergency inlet Pressure

(2)

175 psig (12,1 bar)                  

allowable Outlet Pressures (Casing)

(2)

Emergency: 

10 psig (0,69 bar)

Maximum Operating to avoid internal Part 

Damage: 

5 psig (0,35 bar)

Outlet Pressure Ranges

(2)

See Table 2

Orifice Sizes

See Table 1

Temperature Capabilities

(2)

-20° to 160°F (-29° to 71°C)

Pressure Registration

Internal

Spring Case Vent Connection

1 NPT with removable screen 

(standard)

3/4 NPT with removable screen (optional)

Spring Case Vent and Body Mounting Positions

See Figure 5

External Dimensions

See Figure 6

approximate Weight

4 pounds (2 kg)

OuTlET PRESSuRE RangES

COnTROl SPRing DaTa

Part number

Color

Wire Diameter, inches (mm)

Free length, inches (mm)

4.5 to 6-inches w.c. (11 to 15 mbar)

T13539T0012

Red

0.070 (1,78)

2.50 (63,5)

5.5 to 8-inches w.c. (14 to 20 mbar)

T13527T0012

Yellow

0.067 (1,70)

2.59 (65,8)

7.5 to 9.5-inches w.c. (19 to 24 mbar)

T13563T0012

Olive drab

0.067 (1,70)

3.24 (82,3)

9.5 to 13-inches w.c. (24 to 32 mbar)

T13529T0012

Green

0.075 (1,91)

3.00 (76,2)

13-inches w.c. to 1.5 psig (32 mbar to 0,10 bar)

T13564T0012

Unpainted

0.120 (3,05)

1.93 (49,0)

1.5 to 2.5 psig (0,10 to 0,17 bar)

T13536T0012

Blue

0.120 (3,05)

2.60 (66,0)

Table 2. 

Outlet Pressure Ranges and Control Spring Data

ORiFiCE SizE

ORiFiCE 

COlOR CODE

WiDE-OPEn C

g

 FOR 

REliEF Sizing

MaxiMuM OPERaTing PRESSuRE FOR 

OPTiMuM PERFORManCE

(1)

inches

mm

Psig

bar

1/8

3/16

1/4

3,2

4,8

6,4

Blue

Green

Brown

12.5

28.2

50.0

125

80

60

8,6

5,5

4,1

1.   Maximum operating inlet pressure is 125 psig (8,6 bar) for all orifice sizes.  The optimum performance is based on 2-inches w.c (5 mbar) boost or 1-inch w.c. (2 mbar) droop.

Table 1. 

Orifice Sizes and C

g

 Coefficients

Principle of Operation

Inlet pressure flows through the open orifice around 

the valve disk and disk holder, around the cam stem 

down the remaining length of the orifice tube and into 

the outlet of the regulator body.  However, not all of the 

pressure passes directly from the inlet to the outlet of 

the regulator.  Pressure is channelled through openings 

in the orifice tube and pressurizes the cavity formed by 

the body and diaphragm/diaphragm head/cam stem 

assembly.  When downstream demand is reduced, the 

pressure under the diaphragm increases. This pressure 

overcomes the regulator setting (which is set by a 

spring) and moves the diaphragm assembly upwards.  

This upward motion is transferred to the cam stem which 

in turn bears against the sliding contact point on the 

back side of the disk holder.
The inclined surface of the cam then forces the disk 

holder toward the orifice and reduces gas flow. If a higher 

Содержание S402Y

Страница 1: ... procedures for Type S402Y pressure reducing regulators The Type S402Y is typically used in residential or small commercial applications to reduce gas distribution pressures down to a reduced pressure range from 4 5 inches w c to 2 5 psig 11 0 mbar to 0 17 bar The Type S402Y has an integral high capacity internal relief valve Scope of the Manual This instruction manual provides information on inst...

Страница 2: ...c to 1 5 psig 32 mbar to 0 10 bar T13564T0012 Unpainted 0 120 3 05 1 93 49 0 1 5 to 2 5 psig 0 10 to 0 17 bar T13536T0012 Blue 0 120 3 05 2 60 66 0 Table 2 Outlet Pressure Ranges and Control Spring Data orifice size orifice color code wide open Cg for relief sizing Maximum operating pressure for optimum performance 1 Inches mm Psig bar 1 8 3 16 1 4 3 2 4 8 6 4 Blue Green Brown 12 5 28 2 50 0 125 8...

Страница 3: ... matter lodged between the orifice and the valve disk or a failure in the valve disk the regulator diaphragm assembly moves upwards trying to push the valve disk against the orifice The valve disk and disk holder being pressed against the orifice will prevent the cam stem from being able to travel any further upward in conjunction with the diaphragm assembly The continued leakage of the inlet pres...

Страница 4: ...n positions other than vertically down require additional vent protection from the elements Such protection may be with separate hood shields or the Fisher Y602 Series vents 4 Regulator operation within the ratings does not preclude the possibility of damage from the debris in the lines or from external sources A regulator should be inspected for damage periodically and after any overpressure cond...

Страница 5: ...et pressure to prevent damage caused by reverse pressurization of the regulator The steps below apply to the typical installation as indicated 1 Slowly close the upstream shutoff valve 2 Release downstream pressure and be sure the upstream pressure has been exhausted Maintenance Warning To avoid personal injury or equipment damage from sudden release of pressure or uncontrolled gas do not attempt ...

Страница 6: ...mbly by tilting it toward the outlet so that the cam stem may be pulled up and out of the orifice tube assembly key 7 5 Reassemble in the reverse order of the above procedures Place the diaphragm assembly into position in the lower casing being sure the cam stem key 10 is properly inserted into the orifice tube assembly key 7 Note that the diaphragm plate is marked with Inlet and Outlet Install th...

Страница 7: ...Type S402Y 7 T80288 Figure 3 Type S402Y Pressure Reducing Regulator Assembly 3 11 12 6 10 7 8 22 1 9 13 4 5 16 Apply Lub Sealant ...

Страница 8: ...0 2445 USA Tel 1 763 241 3238 Europe Selmsdorf Germany 23923 Tel 49 0 38823 31 0 For further information visit www emersonprocess com regulators Recommended spare part Delrin is a mark owned by E I du Pont de Nemours and Co Parts List Key Description Part Number 1 Body Cast Iron No Gauge Tap NPS 3 4 NPT T80281T0012 NPS 1 NPT T80282T0012 Outlet Gauge Tap NPS 3 4 NPT T13649T0012 NPS 1 NPT T13649T002...

Отзывы: