background image

Type S402Y

D101838X012

Instruction Manual

Form 5319

March 2009

www.emersonprocess.com/regulators

Type S402Y Pressure Reducing Regulator

!

WaRning

Failure to follow these instructions or 

to properly install and maintain this 

equipment could result in an explosion, 

fire and/or chemical contamination 

causing property damage and personal 

injury or death. 
Fisher

®

 regulators must be installed, 

operated, and maintained in accordance 

with federal, state, and local codes, 

rules and regulations, and 

manufacturer’s instructions. 
if the regulator vents gas or a leak 

develops in the system, service to 

the unit may be required. Failure 

to correct trouble could result in a 

hazardous condition. 
Call a gas service person to service 

the unit.  Only a qualified person must 

install or service the regulator.

introduction

This installation manual covers the installation and 

startup procedures for Type S402Y pressure 

reducing regulators.  
The Type S402Y is typically used in residential 

or small commercial applications to reduce gas 

distribution pressures down to a reduced pressure 

range from 4.5-inches w.c. to 2.5 psig (11,0 mbar          

to 0,17 bar).  The Type S402Y has an integral high 

capacity internal relief valve.

Scope of the Manual

This instruction manual provides information on 

installation, maintenance, and replacement parts for 

Type S402Y pressure-reduction regulators.  

Product Description

The Type S402Y is generally employed in residential 

or small commercial applications in order to reduce 

gas distribution pressures to a specified pressure 

range from 4.5-inches w.c. to 2.5 psig (11,0 mbar to 

0,17 bar).  The Type S402Y has an integral high 

capacity internal relief valve.

Specifications

Specifications for Type S402Y construction are found 

on page 2.  The following information is stamped on 

the regulator at the factory: Type number, orifice size, 

spring range, and date of manufacture.

Figure 1. 

Type S402Y Pressure Reducing Regulator Assembly

Содержание S402Y

Страница 1: ... procedures for Type S402Y pressure reducing regulators The Type S402Y is typically used in residential or small commercial applications to reduce gas distribution pressures down to a reduced pressure range from 4 5 inches w c to 2 5 psig 11 0 mbar to 0 17 bar The Type S402Y has an integral high capacity internal relief valve Scope of the Manual This instruction manual provides information on inst...

Страница 2: ...c to 1 5 psig 32 mbar to 0 10 bar T13564T0012 Unpainted 0 120 3 05 1 93 49 0 1 5 to 2 5 psig 0 10 to 0 17 bar T13536T0012 Blue 0 120 3 05 2 60 66 0 Table 2 Outlet Pressure Ranges and Control Spring Data orifice size orifice color code wide open Cg for relief sizing Maximum operating pressure for optimum performance 1 Inches mm Psig bar 1 8 3 16 1 4 3 2 4 8 6 4 Blue Green Brown 12 5 28 2 50 0 125 8...

Страница 3: ... matter lodged between the orifice and the valve disk or a failure in the valve disk the regulator diaphragm assembly moves upwards trying to push the valve disk against the orifice The valve disk and disk holder being pressed against the orifice will prevent the cam stem from being able to travel any further upward in conjunction with the diaphragm assembly The continued leakage of the inlet pres...

Страница 4: ...n positions other than vertically down require additional vent protection from the elements Such protection may be with separate hood shields or the Fisher Y602 Series vents 4 Regulator operation within the ratings does not preclude the possibility of damage from the debris in the lines or from external sources A regulator should be inspected for damage periodically and after any overpressure cond...

Страница 5: ...et pressure to prevent damage caused by reverse pressurization of the regulator The steps below apply to the typical installation as indicated 1 Slowly close the upstream shutoff valve 2 Release downstream pressure and be sure the upstream pressure has been exhausted Maintenance Warning To avoid personal injury or equipment damage from sudden release of pressure or uncontrolled gas do not attempt ...

Страница 6: ...mbly by tilting it toward the outlet so that the cam stem may be pulled up and out of the orifice tube assembly key 7 5 Reassemble in the reverse order of the above procedures Place the diaphragm assembly into position in the lower casing being sure the cam stem key 10 is properly inserted into the orifice tube assembly key 7 Note that the diaphragm plate is marked with Inlet and Outlet Install th...

Страница 7: ...Type S402Y 7 T80288 Figure 3 Type S402Y Pressure Reducing Regulator Assembly 3 11 12 6 10 7 8 22 1 9 13 4 5 16 Apply Lub Sealant ...

Страница 8: ...0 2445 USA Tel 1 763 241 3238 Europe Selmsdorf Germany 23923 Tel 49 0 38823 31 0 For further information visit www emersonprocess com regulators Recommended spare part Delrin is a mark owned by E I du Pont de Nemours and Co Parts List Key Description Part Number 1 Body Cast Iron No Gauge Tap NPS 3 4 NPT T80281T0012 NPS 1 NPT T80282T0012 Outlet Gauge Tap NPS 3 4 NPT T13649T0012 NPS 1 NPT T13649T002...