6
Technical specifications
6.1
Detection ranges per detector/flame simulator
Table 6-1: Detection ranges per detector/flame simulator
Model
Detector types
Detector sensitivity
settings
Testing distance
Rosemount FS-UVIR-975 975UR (Legacy)
50 ft (15 m)
8 ft (2.5 m)
975UF (Legacy)
60 ft (20 m)
23 ft (7.01 m)
975UR
93 ft (28 m)
8 ft (2.5 m)
975UF
50 ft (15 m)
20 ft (6 m)
Note
•
The minimum distance from the detector is 30 in (75 cm).
•
At extreme temperatures, there is a 15 percent reduction in the testing range.
WARNING
Keep the device in a safe place when not in use.
6.2
General specifications
Temperature range: -4 °F (-20 °C) to 122 °F (50 °C)
Vibration protection: 1 g (10 - 50 Hz)
6.3
Electrical specifications
•
Rechargeable four cell lithium-ion battery:
—
Power: 14.8 V (4 x 3.7 V), maximum current: 0.2 A
—
Charging: 16.8 V (4 x 4.2 V), maximum current: 4 A
•
Battery capacity: 2.6 Ah
•
Charging time: Two hours at 2 A
6.4
Physical specifications
Dimensions: 9 in (230 mm) x 7.3 in (185 mm) x 5.35 in (136 mm)
Weight: 5.5 lb (2.5 kg)
Enclosure: aluminum, heavy duty copper free, black zinc coating
Reference Manual
Technical specifications
00809-0800-4975
May 2022
Rosemount FS-UVIR-975
21
Содержание Rosemount FS-UVIR-975
Страница 1: ...Reference Manual 00809 0800 4975 Rev DD May 2022 Rosemount FS UVIR 975 ...
Страница 4: ...4 ...
Страница 6: ...Contents Reference Manual May 2022 00809 0800 4975 6 Emerson com Rosemount ...
Страница 14: ...Operation Reference Manual May 2022 00809 0800 4975 14 Emerson com Rosemount ...
Страница 18: ...Maintenance Reference Manual May 2022 00809 0800 4975 18 Emerson com Rosemount ...
Страница 20: ...Ordering information Reference Manual May 2022 00809 0800 4975 20 Emerson com Rosemount ...
Страница 26: ...Product certifications Reference Manual May 2022 00809 0800 4975 26 Emerson com Rosemount ...