3
Operation
3.1
Power up the detector
Procedure
After connecting the detector to power, wait up to 60 seconds for the detector to
completed the initial start-up procedure.
Note
Turning on the detector initiates the following sequence of events:
a. The yellow light-emitting diode (LED) flashes at 4 Hz.
b. The built-in test (BIT) is executed.
c. BIT completes.
d. Detector enters Normal mode, indicated by:
•
Flashing green LED at 1 Hz.
•
Fault relay contacts closing.
•
mA output is 4 mA (for models featuring analog [voltage] output, this will be 2
V).
3.2
Test flame detectors
You can use the Rosemount flame simulators to test the Rosemount 975 flame detectors.
You can also use the manual built-in text (BIT) to test the flame detectors.
Table 3-1: Flame simulator compatibility
Rosemount flame simulator model
Rosemount 975 flame detector model
FS-HR-975
Rosemount 975HR
FS-IR-975
Rosemount 975MR
FS-UVIR-975
Rosemount 975UF and 975UR
To test a flame detector:
Procedure
1. Power up the system and wait for up to 60 seconds for the detector to return to
normal status.
The
Power
light-emitting diode (LED) turns on.
2. Ensure all indicators show Normal.
Postrequisites
For full instructions on testing with a flame simulator, see the relevant Reference Manual.
Reference Manual
Operation
00809-1400-4975
February 2022
Rosemount 975
23
Содержание Rosemount 975 Series
Страница 1: ...Reference Manual 00809 1400 4975 Rev AB February 2022 Rosemount 975 Flame Detectors ...
Страница 22: ...Installation Reference Manual February 2022 00809 1400 4975 22 Emerson com Rosemount ...
Страница 28: ...Maintenance Reference Manual February 2022 00809 1400 4975 28 Emerson com Rosemount ...
Страница 36: ...Specifications Reference Manual February 2022 00809 1400 4975 36 Emerson com Rosemount ...
Страница 38: ...Reference data Reference Manual February 2022 00809 1400 4975 38 Emerson com Rosemount ...
Страница 43: ...Reference Manual 00809 1400 4975 February 2022 Rosemount 975 43 ...