Quick Installation Guide
00825-0100-4004, Rev DB
December 2011
Rosemount 8800D
18
IF
FISCO for Class I, Division 1, Groups A, B, C, and D;
FNICO for Class 1 Division 2, Groups A, B, C, and D.
Temperature Code T4 (-50 °C
T
a
60 °C).
When installed per Rosemount drawing 08800-0112
Enclosure Type 4X
K6
E6 and I6 Combination
Combination Certifications
KB
E5, I5, E6, and I6 Combination
European Certifications
ATEX Intrinsic Safety
EN 60079-0 : 2009
EN 60079-11 : 2007
I1
Certification No. Baseefa05ATEX0084X
ATEX Marking
II 1 G
Ex ia IIC T4 Ga (-60 °C
T
a
70 °C) 4-20 HART
(-60 °C
T
a
60 °C) Fieldbus
0575
ATEX FISCO/FNICO
IA
Certification No. Baseefa05ATEX0084X
ATEX Marking
II 1 G
Ex ia IIC T4 Ga (-60 °C
Ta
60 °C)
0575
Input Parameters:
U
i
= 17.5 Vdc
I
i
= 380 mA
P
i
= 5.32 W
C
i
= 0
F
L
i
< 10
H
Special conditions for safe use (x)
When fitted with 90V transient suppressors (T1 Option), the equipment is not capable of
passing the 500V isolation test. This must be taken into account upon installation.
4-20 mA HART
Entity Parameters
Fieldbus Entity
Parameters
U
i
= 30 VDC
U
i
= 30 VDC
I
i
(1)
(1)
Total for transmitter
= 185 mA
I
i
= 300 mA
P
i
(1)
= 1.0 W
P
i
= 1.3 W
C
i
= 0
F
C
i
= 0
F
L
i
< 0.97 mH
L
i
< 10
4004_RevDB.fm Page 18 Wednesday, November 23, 2011 3:06 PM
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com