5
Connect wiring and power up
5.1
Power supply
The dc power supply should provide power with less than two percent ripple.
The total resistance load is the sum of the resistance of the signal leads and
the load resistance of the controller, indicator, and related pieces. Note that
the resistance of intrinsic safety barriers, if used, must be included.
Load limitation
Figure 5-1:
C
A
B
B
D
1500
1250
1000
750
500
250
0
10.8 16.8
22.8
28.8
34.8
42
A. Rloop in ohms
B. Power supply voltage
Maximum Loop Resistance = 41.7 (Power Supply Voltage - 10.8) The Field
Communicator requires a minimum loop resistance of 250 ohms.
5.2
Conduit installation
Prevent condensation in any conduit from flowing into the housing by
mounting the flowmeter at a high point in the conduit run. If the flowmeter is
mounted at a low point in the conduit run, the terminal compartment could
fill with fluid.
If the conduit originates above the flowmeter, route conduit below the
flowmeter before entry. In some cases a drain seal may need to be installed.
April 2018
Quick Start Guide
Quick Start Guide
13
Содержание Rosemount 8600D Series
Страница 1: ...Quick Start Guide 00825 0100 4860 Rev EB April 2018 Rosemount 8600 Series Vortex Flowmeter ...
Страница 35: ...April 2018 Quick Start Guide Quick Start Guide 35 ...
Страница 36: ...Quick Start Guide April 2018 36 Rosemount 8600 Series Vortex Flowmeter ...
Страница 37: ...April 2018 Quick Start Guide Quick Start Guide 37 ...
Страница 38: ...Quick Start Guide April 2018 38 Rosemount 8600 Series Vortex Flowmeter ...
Страница 39: ...April 2018 Quick Start Guide Quick Start Guide 39 ...