Configuration
July 2018
Configuration
2.8.3
Configure alarm and saturation levels
In normal operation, the transmitter will drive the output in response to measurements between the
lower to upper saturation points. If the temperature goes outside the sensor limits, or if the output
would be beyond the saturation points, the output will be limited to the associated saturation point.
The Rosemount 644 Transmitter automatically and continuously performs self-diagnostic routines. If the
self-diagnostic routines detect a failure, the transmitter drives the output to configured alarm value
based on the position of the alarm switch. The Alarm and Saturation settings allow the alarm settings (Hi
or Low) and saturation values to be viewed and changed.
Failure mode alarm and saturation levels can be configured using a Field Communicator, AMS Device
Manager, and the LOI. The following limitations exist for custom levels:
The low alarm value must be less than the Low Saturation level.
The high alarm value must be higher than the High Saturation level.
Alarm and Saturation levels must be separated by at least 0.1 mA
The configuration tool will provide an error message if the configuration rule is violated.
See table below for the common alarm and saturation levels.
Note
Transmitters set to HART multi-drop mode send all saturation and alarm information digitally; saturation
and alarm conditions will not affect the analog output.
Table 2-4. Rosemount Alarm and Saturation Values
Units - mA
Min
Max
Rosemount
Namur
High alarm
21
23
21.75
21.0
Low alarm
(1)
1.
Requires 0.1 mA gap between low alarm and low saturation values.
3.5
3.75
3.75
3.6
High saturation
20.5
22.9
(2)
2.
Rail mount transmitters have a high saturation max of 0.1 mA less than the high alarm setting, with a max value
of 0.1 mA less than the high alarm max.
20.5
20.5
Low saturation
3.6
(3)
3.
Rail mount transmitters have a low saturation min of 0.1 mA greater than the low alarm setting, with a
minimum of 0.1 mA greater than the low alarm min.
3.9
3.9
3.8
Содержание Rosemount 644 with HART Protocol
Страница 2: ......
Страница 8: ...vi Reference Manual 00809 0200 4728 Rev SA Title Page July 2018 Title Page ...
Страница 48: ...40 Reference Manual 00809 0200 4728 Rev SA Configuration July 2018 Configuration ...
Страница 62: ...54 Reference Manual 00809 0200 4728 Rev SA Installation July 2018 Installation ...
Страница 72: ...64 Reference Manual 00809 0200 4728 Rev SA Operation and Maintenance July 2018 Operation and Maintenance ...
Страница 96: ...Reference Data July 2018 Reference Manual 00809 0200 4728 Rev SA Specifications and Reference Data 88 ...
Страница 111: ......