5
Reference Manual
00809-0200-4728, Rev SA
Configuration
July 2018
Configuration
2.3.2
Surges/transients
The transmitter will withstand electrical transients of the energy level encountered in static discharges or
induced switching transients. However, high-energy transients, such as those induced in wiring from
nearby lightning strikes, welding, heavy electrical equipment, or switching gears, can damage both the
transmitter and the sensor. To protect against high-energy transients, install the transmitter into a
suitable connection head with the integral transient protector, option T1. Refer to the Rosemount 644
for more information.
2.4
Configuration methods
The Rosemount 644 Transmitter can be configured either before or after installation. Configuring the
transmitter on the bench using either a Field Communicator, AMS Device Manager, or LOI ensures all
transmitter components are in working order prior to installation.
The Rosemount 644 Transmitter can be configured either on-line or off-line using a Field Communicator,
AMS Device Manager or the optional LOI (Head mount and field mount). During on-line configuration,
the transmitter is connected to a Field communicator. Data is entered in the working register of the
communicator and sent directly to the transmitter.
Off-line configuration consists of storing configuration data in a Field Communicator while it is not
connected to a transmitter. Data is stored in nonvolatile memory and can be downloaded to the
transmitter at a later time.
2.4.1
Configuring on the bench
To configure on the bench, required equipment includes a power supply, a digital multimeter (DMM),
and Field Communicator, AMS Device Manager, or a LOI – option M4.
Connect the equipment as shown in
. Connect HART Communication leads at any termination
point in the signal loop. To ensure successful HART Communication, a resistance of at least 250 Ohms
must be present between the transmitter and the power supply. Connect the Field Communicator leads
to the clips behind the power (+,–) terminals on the top of the device. Avoid exposing the transmitter
electronics to the plant environment after installation by setting all transmitter jumpers during the
commissioning stage on the bench.
Table 2-1. Rosemount 644 Device Revisions and Files
Software date
Identify device
Find device driver files
Review instructions
Review
functionality
Date
NAMUR Software
Revision
HART Software
Revision
HART Universal
Revision
(1)
1.
NAMUR Software Revision is located on the hardware tag of the device. HART Software Revision can be read using a HART Communication tool.
Device
Revision
(2)
2.
Device Driver file names use Device and DD Revision, e.g. 10_01. HART Protocol is designed to enable legacy device driver revisions to continue to communicate with
new HART devices. To access new functionality, the new Device Driver must be downloaded. It is recommended to download the new Device Driver files to ensure full
functionality.
Document
Changes to
Software
(3)
3.
HART Revision 5 and 7 Selectable. Dual Sensor support, Safety Certified, Advanced Diagnostics (if ordered), Enhanced Accuracy and Stability (if ordered).
June 2012
1.1.1
01
5
8
Rosemount 644
Temperature Transmitter
for list of changes
7
9
Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter
electronics to the plant environment after installation.
Содержание Rosemount 644 with HART Protocol
Страница 2: ......
Страница 8: ...vi Reference Manual 00809 0200 4728 Rev SA Title Page July 2018 Title Page ...
Страница 48: ...40 Reference Manual 00809 0200 4728 Rev SA Configuration July 2018 Configuration ...
Страница 62: ...54 Reference Manual 00809 0200 4728 Rev SA Installation July 2018 Installation ...
Страница 72: ...64 Reference Manual 00809 0200 4728 Rev SA Operation and Maintenance July 2018 Operation and Maintenance ...
Страница 96: ...Reference Data July 2018 Reference Manual 00809 0200 4728 Rev SA Specifications and Reference Data 88 ...
Страница 111: ......