6
Reference Manual
00809-0700-4001, Rev AA
Configuration
May 2017
Configuration
2.3
HART installation flowchart
Figure 2-1. HART Installation Flowchart
START HERE
Bench
Calibration?
Field Install
No
Set Units
(
Set Range Points
(
Select Linear
Output
)
Set Damping
)
Verify
Apply Pressure
Yes
Within
Specifications?
Yes
No
Refer to
Configure
Security and
Alarm
(
)
Mount Transmitter
Wire Transmitter
(
)
Power Transmitter
(
Trim the
Transmitter
(
Done
Review Transmitter
Configuration
Confirm Transmitter
Configuration
(
Configure for
Pressure
Check Process
Connection
)