Note
Improper grounding is the most frequent cause of poor
segment communications.
3. Replace the housing cover. It is recommended that the cover be
tightened until there is no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
Note
The Rosemount 3051HT polished 316 SST housing only provides
ground termination inside the terminal compartment.
Power supply
The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic
safety) to operate and provide complete functionality.
Power conditioner
A Fieldbus segment requires a power conditioner to isolate the power
supply, filter, and decouple the segment from other segments attached to
the same power supply.
Grounding
Signal wiring of the Fieldbus segment can not be grounded. Grounding out
one of the signal wires will shut down the entire Fieldbus segment.
Shield wire ground
To protect the Fieldbus segment from noise, grounding techniques for
shield wire require a single grounding point for shield wire to avoid creating
a ground loop. Connect the cable shields for the entire segment to a single
good earth ground at the power supply.
Signal termination
For every Fieldbus segment a terminator should be installed at the beginning
and at the end of each segment.
Locating devices
Devices are frequently installed, configured, and commissioned over time by
different personnel. A “Locate Device” capability uses the LCD display (when
installed) to assist personnel in finding the desired device.
From the device Overview screen, select the Locate Device button. This will
launch a method allowing the user to display a “Find me” message or enter a
custom message to display on the device LCD display. When the user exits
the “Locate Device” method, the device LCD display automatically returns to
normal operation.
June 2020
Quick Start Guide
Quick Start Guide
11
Содержание Rosemount 3051HT
Страница 25: ...Figure 3 1 Rosemount 3051HT Declaration of Conformity June 2020 Quick Start Guide Quick Start Guide 25 ...
Страница 26: ...Figure 3 2 Rosemount 3051HT Declaration of Conformity Quick Start Guide June 2020 26 Emerson com Rosemount ...
Страница 27: ...Figure 3 3 Rosemount 3051HT Declaration of Conformity June 2020 Quick Start Guide Quick Start Guide 27 ...
Страница 28: ...China RoHS Quick Start Guide June 2020 28 Emerson com Rosemount ...
Страница 29: ...June 2020 Quick Start Guide Quick Start Guide 29 ...
Страница 30: ...Quick Start Guide June 2020 30 Emerson com Rosemount ...
Страница 31: ...June 2020 Quick Start Guide Quick Start Guide 31 ...