Quick Start Guide

00825-0200-4091, Rev CA

June 2020

Rosemount

 3051HT Hygienic Pressure

Transmitter

with F

OUNDATION

 Fieldbus Protocol

Содержание Rosemount 3051HT

Страница 1: ...Quick Start Guide 00825 0200 4091 Rev CA June 2020 Rosemount 3051HT Hygienic Pressure Transmitter with FOUNDATION Fieldbus Protocol ...

Страница 2: ...ocess leaks could result in death or serious injury To avoid process leaks only use the gasket designed to seal with the corresponding flange adapter ph Physical access Unauthorized personnel may potentially cause significant damage to and or misconfiguration of end users equipment This could be intentional or unintentional and needs to be protected against Physical security is an important part o...

Страница 3: ...evision 8 and Drivers FOUNDATION Fieldbus device revision can be read using a FOUNDATION Fieldbus capable configuration tool Host Device driver DD 1 Obtain at Device driver DTM Manual document number All DD4 DD Rev 1 FieldCommGroup org Emerson com 00809 0100 47 74 Rev CA or newer All DD5 DD Rev 1 FieldCommGroup org Emerson AMS Device Manager V 10 5 or higher DD Rev 2 Emerson com Emerson AMS Device...

Страница 4: ...ght dustproof conduit seal and meets requirements of NEMA Type 4X IP66 IP68 and IP69K Consult factory if other Ingress Protection ratings are required Note IP69K rating only available on units with a SST housing and option code V9 in the model string For M20 threads install conduit plugs to full thread engagement or until mechanical resistance is met In line gauge transmitter orientation The low s...

Страница 5: ...ressure port atmospheric reference Clamping When installing clamp follow recommended torque values provided by gasket manufacturer Note To maintain performance torquing a 1 5 in Tri Clamp beyond 50 in lb is not recommended on pressure ranges below 20 psi June 2020 Quick Start Guide Quick Start Guide 5 ...

Страница 6: ... 3 Commissioning Tag A Commissioning Tag DEVICE ID 001151AC00010001440 121698091725 DEVICE REVISION PHYSICAL DEVICE TAG DEVICE ID 001151AC00010001440 121698091725 DEVICE REVISION S N PHYSICAL DEVICE TAG Device Barcode A Device revision Note The device description loaded in the host system must be at the same revision as this device The device description can be downloaded from the host system webs...

Страница 7: ...on of the transmitter Note Default security is off Setting the simulate switch The security switch can be enabled or disabled in the software Procedure 1 If the transmitter is installed secure the loop and remove power 2 Remove the housing cover opposite the field terminal side WARNING Explosions could result in death or serious injury In an explosion proof flameproof installation do not remove th...

Страница 8: ... software simulate parameter must be disabled through the host Procedure 1 If the transmitter is installed secure the loop and remove power 2 Remove the housing cover opposite the field terminal side WARNING Explosions could result in death or serious injury In an explosion proof flameproof installation do not remove the transmitter covers when power is applied to the unit 3 Slide the simulate swi...

Страница 9: ...ace when tightening the terminal block screw No additional power is needed Note The use of a pin or a ferrule wire terminal is not recommended as the connection may be more susceptible to loosening over time or under vibration 3 Ensure proper grounding It is important the instrument cable shield be a Trimmed close and insulated from touching the transmitter housing b Connected to the next shield i...

Страница 10: ...hen transient protect terminal blocks are installed or to fulfill local regulations Procedure 1 Remove the field terminals housing cover 2 Connect the wiring pair and ground as indicated in Figure 2 5 a Trim the cable shield as short as practical and insulate from touching the transmitter housing Note Do NOT ground the cable shield at the transmitter if the cable shield touches the transmitter hou...

Страница 11: ...e entire Fieldbus segment Shield wire ground To protect the Fieldbus segment from noise grounding techniques for shield wire require a single grounding point for shield wire to avoid creating a ground loop Connect the cable shields for the entire segment to a single good earth ground at the power supply Signal termination For every Fieldbus segment a terminator should be installed at the beginning...

Страница 12: ...on tool support these features Use the following block examples to do basic configuration to the transmitter For more advanced configurations see the Rosemount 3051 FOUNDATION Fieldbus Reference Manual Note DeltaV users should use DeltaV Explorer for the resource and transducer blocks and Control Studio for the function blocks 2 5 1 Configure the AI block Navigation instructions for each step are ...

Страница 13: ...s Channel Mapping Master Reset Process Variable Pressure Pressure Damping Sensor Temperature Change Damping 7 9 Security Simulation Write Lock Setup Guided Setup Zero Trim Change Damping Local Display Setup Configure Analog Input Blocks 3 4 5 9 8 9 8 9 7 9 Classic View Display 2 10 Standard Text Navigation selections available Text Name of selection used on parent menu screen to access this screen...

Страница 14: ...figuration This procedure is for the guided setup of the AI Block Configuration Prerequisites Navigate to Configure Guided Setup Procedure 1 Select AI Block Unit Setup 2 Select the signal conditioning L_TYPE from the menu Select Direct for pressure measurements using the device default units Select Indirect for other pressure or level units 3 Set the XD_SCALE to the 0 and 100 scale points the tran...

Страница 15: ... in seconds The permitted range of values is 0 4 to 60 seconds 7 To configure the LCD display if installed 8 Select Local Display Setup 9 Check the box next to each parameter to be displayed to a maximum of four parameters The LCD display will continuously scroll through the selected parameters 10 To review the transmitter configuration navigate using the manual setup navigation sequences for AI B...

Страница 16: ...p LCDdisplay 6 Set lowcutoff LOW_CUT 9 Review transmitter configuration 3 Set signal conditioning L_TYPE 5 Set scaling OUT_SCALE 2 Check switches and software write lock Done 10 Set switches and software write lock 4 Set scaling XD_SCALE Note For convenience AI block 1 is pre linked to the transmitter primary variable and should be used for this purpose AI block 2 is pre linked to the transmitter ...

Страница 17: ...s Direct the AI block may be placed in AUTO mode to return the device to service 6 If the L_TYPE selected is Indirect or Indirect Square Root set OUT_SCALE to change engineering units a Select OUT_SCALE UNITS from the menu b Set the OUT_SCALE low value This may be elevated or suppressed for level applications c Set the OUT_SCALE high value This may be elevated or suppressed for level applications ...

Страница 18: ...e Note If hardware or software write protection is not needed Step 16 can be skipped 16 Set switches and software write lock a Check switches see Figure 2 4 Note The write lock switch can be left in the locked or unlocked position The simulate enable disable switch may be in either position for normal device operation 2 5 5 Enable software write lock Procedure 1 Navigate from the Overview screen a...

Страница 19: ... units 1 Select only the units that are supported by the device Table 2 1 Pressure example Parameters Enter data Channel 1 L_Type Direct XD_Scale See list of supported engineering units 1 Out_Scale Set values outside operating range 1 Select only the units that are supported by the device 2 5 7 Display pressure on the LCD display Select the Pressure check box on the Display Configuration screen 2 ...

Страница 20: ...rrors compensate for the offset by using the XD_Scaling Out_Scaling and Indirect L_Type which are part of the AI Block Configure Procedure Guided Setup 1 Navigate to Configure Guided Setup 2 Select Zero Trim The method will execute the zero trim Manual Setup 3 Navigate to Overview Calibration Sensor Trim 4 Select Zero Trim The method will execute the zero trim Quick Start Guide June 2020 20 Emerso...

Страница 21: ...nclosure 2 non metallic enclosure 3 3 Installing Equipment in North America The US National Electrical Code NEC and the Canadian Electrical Code CEC permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions The markings must be suitable for the area classification gas and temperature class This information is clearly defined in the respective codes 3 4 USA I5 Intr...

Страница 22: ...20 C Ta 60 C Table 3 1 Input Parameters Parameter HART Fieldbus PROFIBUS Voltage Ui 30 V 30 V Current Ii 200 mA 300 mA Power Pi 0 9 W 1 3 W Capacitance Ci 0 012 µF 0 µF Inductance Li 0 mH 0 mH Special Conditions for Safe Use X 1 The apparatus is not capable of withstanding the 500 V insulation test required by clause 6 3 12 of EN60079 11 2012 This must be taken into account when installing the app...

Страница 23: ...paint finish however care should be taken to protect it from impact or abrasion if located in Zone 0 3 8 Brazil I2 INMETRO Intrinsic Safety Certificate UL BR 13 0584X Standards ABNT NBR IEC60079 0 2008 Errata 1 2011 ABNT NBR IEC60079 11 2009 Markings HART Ex ia IIC T5 T4 Ga T5 20 C Ta 40 C T4 20 C Ta 70 C Fieldbus Ex ia IIC T4 Ga 20 C Ta 60 C HART PROFIBUS Voltage Ui 30 V 30 V Current Ii 200 mA 30...

Страница 24: ...l Rosemount 3051HT transmitters with the following connections are EHEDG approved and labeled T32 1 in Tri Clamp T42 2 in Tri Clamp If process connection B11 is selected see reference the ordering table of the Rosemount 1199 Diaphragm Seal PDS 00813 0100 4016 for availability of EHEDG certifications An EHEDG certificate of compliance is available by selecting option code QE Ensure gasket selected ...

Страница 25: ...Figure 3 1 Rosemount 3051HT Declaration of Conformity June 2020 Quick Start Guide Quick Start Guide 25 ...

Страница 26: ...Figure 3 2 Rosemount 3051HT Declaration of Conformity Quick Start Guide June 2020 26 Emerson com Rosemount ...

Страница 27: ...Figure 3 3 Rosemount 3051HT Declaration of Conformity June 2020 Quick Start Guide Quick Start Guide 27 ...

Страница 28: ...China RoHS Quick Start Guide June 2020 28 Emerson com Rosemount ...

Страница 29: ...June 2020 Quick Start Guide Quick Start Guide 29 ...

Страница 30: ...Quick Start Guide June 2020 30 Emerson com Rosemount ...

Страница 31: ...June 2020 Quick Start Guide Quick Start Guide 31 ...

Страница 32: ... 1046 CH 6340 Baar Switzerland 41 0 41 768 6111 41 0 41 768 6300 RFQ RMD RCC Emerson com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 65 6777 8211 65 6777 0947 Enquiries AP Emerson com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 ...