Reference Manual
00809-0100-4100, Rev AA
Section 3: Installation
June 2012
Mounting Requirements
for examples of the following mounting configurations:
Liquid Flow Measurement
Place taps to the side of the line to prevent sediment deposits on the process isolators.
Mount the transmitter beside or below the taps so gases vent into the process line.
Mount drain/vent valve upward to allow gases to vent.
Gas Flow Measurement
Place taps in the top or side of the line.
Mount the transmitter beside or above the taps so to drain liquid into the process line.
Steam Flow Measurement
Place taps to the side of the line.
Mount the transmitter below the taps to ensure that impulse piping will remain filled
with condensate.
Fill impulse lines with water to prevent steam from contacting the transmitter directly
and to ensure accurate measurement start-up.
Note
For steam or other elevated temperature services, it is important that temperatures at the
Coplanar process flanges must not exceed 250 °F (121 °C) for transmitters with silicone fill, or
185 °F (85 °C) for inert fill. For vacuum service, these temperature limits are reduced to 220 °F
(104 °C) for silicone fill and 160 °F (71 °C) for inert fill.
3.4.2
Process Connections
3051 Wireless transmitter flange process connection size is
1
/
4
–18 NPT. Flange adapters with
1
/
2
–14 NPT connections are available as the D2 option. Use your plant-approved lubricant or
sealant when making the process connections. The process connections on the transmitter
flange are on 2
1
/
8
-inch (54 mm) centers to allow direct mounting to a three-valve or five-valve
manifold. Rotate one or both of the flange adapters to attain connection centers of 2 inches
(51 mm), 2
1
/
8
inches (54 mm), or 2
1
/
4
inches (57 mm).
Install and tighten all four flange bolts before applying pressure to avoid leakage. When properly
installed, the flange bolts will protrude through the top of the sensor module housing. Do not
attempt to loosen or remove the flange bolts while the transmitter is in service.
To install adapters to a Coplanar flange, perform the following procedure:
1.
Remove the flange bolts.
2.
Leaving the flange in place, move the adapters into position with the O-ring installed.
3.
Clamp the adapters and the Coplanar flange to the transmitter module using the longer
of the bolts supplied.
4.
Tighten the bolts. Refer to
for torque specifications.
Содержание Rosemount 2051 Wireless Series
Страница 2: ......
Страница 12: ...4 Reference Manual 00809 0100 4102 Rev AA Section 1 Introduction June 2012 Introduction ...
Страница 32: ...24 Reference Manual 00809 0100 4102 Rev AA Section 2 Configuration June 2012 Configuration ...
Страница 105: ...118 Reference Manual 00809 0100 4102 Rev AA Appendix A Reference Data June 2012 Specifications and Reference Data ...
Страница 109: ...122 Reference Manual 00809 0100 4102 Rev AA Appendix B Product Certifications June 2012 Product Certifications ...
Страница 110: ......
Страница 113: ......
Страница 117: ...iv Reference Manual 00809 0100 4100 Rev AA Title Page June 2012 ...
Страница 123: ...x Reference Manual 00809 0100 4100 Rev AA Table of Contents June 2012 Table of Contents ...
Страница 167: ...44 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Страница 168: ...45 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Страница 169: ...46 Reference Manual 00809 0100 4100 Rev AA Section 3 Installation June 2012 Installation ...
Страница 248: ...146 Reference Manual 00809 0100 4100 Rev AA Appendix B Product Certifications June 2012 Product Certifications ...
Страница 249: ......