1 PRODUCT DESCRIPTION
Figure 1.1 Model number nomenclature
1.1 Prop Fan Condensing Units
Liebert® propeller fan condensing units are available in a range of sizes and configurations to offer
flexibility in designing a precision environmental control system. The appropriate propeller fan
condensing unit paired with a corresponding Liebert fan coil evaporator model such as Liebert
DataMate™, Liebert Mini-Mate2™ or Liebert Challenger 3000™ is an effective solution for your
environmental control application requirements.
Split system condensing units are connected to the evaporator unit by two refrigerant lines (four in 8-ton
systems) and a low-voltage control cable. The condensing unit requires a separate power source and
power disconnect switch.
1.1.1 Base System 95°F (35°C) Ambient Models
The heart of the refrigeration system is a quiet, high efficiency scroll compressor with internal vibration
isolation mountings, pressure safety controls and built-in overload protection. Standard features include
crankcase heater, high-pressure switch, condenser coil, sight glass, filter drier, hot gas bypass system with
liquid quenching valve, direct drive propeller fan and motor, and Liebert Lee-Temp™ flood-back head
pressure control. These models are designed to provide catalog capacity of the appropriate evaporator
section up to 95°F (35°C) outside ambient temperature.
1.1.2 105°F (41°C) Ambient Models
These models contain similar components to the base models except the coils and fans are sized to
provide catalog capacity of the appropriate evaporator section up to 105°F (41°C) outside ambient
temperature.
1.1.3 Liebert Quiet-Line
™
Models
These models contain similar components to the base models except the coils and fans are sized to
provide catalog capacity of the appropriate evaporator section up to 95°F (35°C) outside ambient
temperature with a noise level of less than 58 dBA.
Vertiv
| Liebert PFH Installer/User Guide |
1
Содержание PFH020A-L
Страница 2: ...Precision Cooling For Business Critical Continuity Liebert Mini Mate2 User Manual 1 1 5 Tons 50 60Hz ...
Страница 3: ......
Страница 74: ...Liebert Prop Fan Condensing Unit 50 Hz and 60 Hz Installer User Guide ...
Страница 77: ...5 Troubleshooting 37 Vertiv Liebert PFH Installer User Guide ii ...
Страница 83: ...Figure 2 3 Dimensional data 277V step down transformer Vertiv Liebert PFH Installer User Guide 6 ...
Страница 86: ...Figure 2 6 General piping arrangement Vertiv Liebert PFH Installer User Guide 9 ...
Страница 87: ...Figure 2 7 Electrical field connections 1 to 5 ton units Vertiv Liebert PFH Installer User Guide 10 ...
Страница 88: ...Figure 2 8 Electrical field connections 8 ton units Vertiv Liebert PFH Installer User Guide 11 ...
Страница 89: ...Figure 2 9 Single phase 1 3 ton model schematic typical Vertiv Liebert PFH Installer User Guide 12 ...
Страница 90: ...Figure 2 10 Three phase 3 5 ton model schematic typical Vertiv Liebert PFH Installer User Guide 13 ...
Страница 105: ...Vertiv Liebert PFH Installer User Guide 28 This page intentionally left blank ...
Страница 109: ...Vertiv Liebert PFH Installer User Guide 32 This page intentionally left blank ...
Страница 116: ......