User Manual
Chapter 2
GFK-1503F
Jan 2020
CPU Module Datasheets: CPU001, CPU002, CPU005
20
FAULT
ON if the CPU is in Stop/Faulted mode because a fatal fault has
occurred.
To turn off the Fault LED, clear both the I/O Fault Table and the PLC Fault
Table. If this LED is blinking and the OK LED is OFF, a fatal fault was
detected during PLC powerup diagnostics. Contact PLC Field Service.
FORCE
ON if an override is active on a bit reference.
PORT 1
PORT 2
Blinking indicates activity on that port.
2.7
Configurable Memory
CPU001 and CPU002 (release 2.0 or later) and CPU005 have configurable user memory. The
configurable memory is the amount of memory required for the application program,
hardware configuration, registers (%R), analog inputs (%AI), and analog outputs (%AQ).
The amount of memory allocated to the application program and hardware configuration
are automatically determined by the actual program and configuration entered from the
programmer. The rest of the configurable memory can be easily allocated to suit the
application.
Configurable memory
CPU001: 34K bytes maximum CPU002: 42K
bytes maximum CPU005: 128K bytes
maximum
Application program size (not configurable)
CPU001, for rel. 1.50 compatibility
CPU002, for rel. 1.50 compatibility
128 bytes minimum
12K bytes
20K bytes
Hardware configuration size (not configurable)
400 bytes minimum
Registers (%R)
CPU001/002, for rel. 1.50 compatibility
256 bytes minimum
4,096 bytes
Analog Inputs (%AI)
256 bytes minimum
Analog Outputs (%AQ)
256 bytes minimum